User Manual
Controller
Parameter Description
URL EnterURLtotheOPCUAserver.
OnlyUATCP Binaryiss upported whichmeansthe URLmust
startwith“opc.tcp://”
Authentication
settings
Choosewhetherto useanonymousloginorentera user
nameandpasswordtoenableasecuredlogin.
Namespacesettings Thissettingoffersapossibility todeclareanamespaceURI
andbindittoaprefix.
Namespaceseparator character: Enteracharactertobe
usedtoseparate thenamespaceURIprefixfromthetagID
whenpresentedonthetagtab.
TagViewsettings
Defaultnamespace: Select thedefaultnamespaceURI
prefixtobeusedwhenenteringatagonthetagtab.
Maxsubscriptions: Enterthemaximumnumber of
subscriptionssupportedbytheserver
(1)
Subscription settings
Maxitemspersubscription : Enterthemaximumnumber
ofitemspersubscriptionsupportedbytheserver
(1)
(1)
Pleaser
efertothe servermanualfor limitations
AddTagsfrom OPCUAServer
Add OPC UA server tags by clicking the Add button on the Tags tab.
Enter the Tag ID along with the preferred namespace URI prefix, defined in the
controller settings dialog. Make sure to separate the values with the separator
character.
Example: “NS3:tag”.
The Tag ID, in the example above, corresponds with BrowseName in the OPC
UA server.