Manual

DIP Switches
Beijer Electronics, MAEN956 41
10 DIP Switches
The serial interfaces mode as well as the monitor address can be adjusted via the
DIP switches.
By default, all DIP switches are set to OFF. This means that the monitor is set
to address 0 and RS232 mode.
4 DIP switches are used to set addresses, and 16 addresses can be realized binary
(0 – 15), which means that 16 monitors can be connected via RS485.
Serial Mode
Monitor Addresses
DIP switch 1 Mode
ON RS485
OFF RS232 (default)
Address DIP switch 2 DIP switch 3 DIP switch 4 DIP switch 5
0 OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3ONONOFFOFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7ONONONOFF
8 OFF OFF OFF ON
9ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14OFFONONON
15 ON ON ON ON