Owner manual
2
AC Supply Voltage
(50 / 60Hz)
L1 L2 L3
Earth L N
Fuses or MCB
Supply Voltage :
- 110-115, 200-240, 400-480 +/- 10%
- 1 or 3 Phase
- Check the drive rating information on page 28
Fuses or MCB, Cable Sizes :
- Check the drive rating information on page 28
- Recommended cable sizes shown on page 28
-
Keypad operation can be found on page 17
Control Terminals :
Based on the default, out of box settings –
- Connect a Start / Stop switch between terminals 1 & 2
- Close the switch to start
- Open the switch to stop
- Connect a potentiometer (5kΩ minimum) terminals 5, 6 &
7 to vary the speed from minimum (0Hz) to maximum (50
/ 60Hz)
-
Motor Cable Sizes
- Check the rating information on page 28
- For EMC compliance, use a shielded type cable
Motor Connections
- Check for Star or Delta connection according to the motor
voltage rating (See page 13)
Motor Nameplate Details
- Enter the motor rated voltage in P-07
- Enter the motor rated current in P-08
- Enter the motor rated frequency in P-09
IP20 Easy Start-Up Guide
RJ45
Connector
Mechanical Mounting
- Information can be found on page 10