User Manual

User Guide Revision 1.12
64
12.2.2. Modbus Control & Monitoring Registers
The following is a list of accessible Modbus Registers available in the drive.
Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source (P1-12 = 4)
Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is enabled
(P5-07 = 1)
Registers 6 to 24 can be read regardless of the setting of P1-12
Register
Number
Upper Byte
Lower Byte
Read
Write
Notes
1
Command Control Word
R/W
Command control word used to control the drive when operating with Modbus RTU.
The Control Word bit functions are as follows :-
Bit 0 : Run/Stop command. Set to 1 to enable the drive. Set to 0 to stop the drive.
Bit 1 : Fast stop request. Set to 1 to enable drive to stop with 2
nd
deceleration ramp.
Bit 2 : Reset request. Set to 1 in order to reset any active faults or trips on the drive.
This bit must be reset to zero once the fault has been cleared.
Bit 3 : Coast stop request. Set to 1 to issue a coast stop command.
2
Command Speed Reference
R/W
Set-point must be sent to the drive in Hz to one decimal place, e.g. 500 = 50.0Hz
3
Command Torque Reference
R/W
Set-point must be sent to the drive in % to one decimal place, e.g. 2000 = 200.0%
4
Command Ramp times
R/W
This register specifies the drive acceleration and deceleration ramp times used when
Fieldbus Ramp Control is selected (P5-08 = 1) irrespective of the setting of P1-12. The
input data range is from 0 to 60000 (0.00s to 600.00s)
6
Error code
Drive status
R
This register contains 2 bytes.
The Lower Byte contains an 8 bit drive status word as follows :-
Bit 0 : 0 = Drive Disabled (Stopped), 1 = Drive Enabled (Running)
Bit 1 : 0 = Drive Healthy, 1 = Drive Tripped
The Upper Byte will contain the relevant fault number in the event of a drive trip.
Refer to section 15.1 for a list of fault codes and diagnostic information
7
Output Frequency
R
Output frequency of the drive to one decimal place, e.g.123 = 12.3 Hz
8
Output Current
R
Output current of the drive to one decimal place, e.g.105 = 10.5 Amps
9
Output Torque
R
Motor output torque level to one decimal place, e.g. 474 = 47.4 %
10
Output Power
R
Output power of the drive to two decimal places, e.g.1100 = 11.00 kW
11
Digital Input Status
R
Represents the status of the drive inputs where Bit 0 = Digital Input 1 etc
20
Analog 1 Level
R
Analog Input 1 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%
21
Analog 2 Level
R
Analog Input 2 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%
22
Pre Ramp Speed Reference
R
Internal drive frequency set-point
23
DC bus voltages
R
Measured DC Bus Voltage in Volts
24
Drive temperature
R
Measured Heatsink Temperature in °C
12.2.3. Modbus Parameter Access
All User Adjustable parameters (Groups 1 to 5) are accessible by Modbus, except those that would directly affect the Modbus
communications, e.g.
P5-01 Drive Fieldbus Address
P5-03 Modbus RTU Baud Rate
P5-04 Modbus RTU Data Format
All parameter values can be read from the drive and written to, depending on the operating mode of the drive some parameters cannot be
changed whilst the drive is enabled for example.
When accessing a drive parameter via Modbus, the Register number for the parameter is the same as the parameter number,
E.g. Parameter P1-01 = Modbus Register 101.
Modbus RTU supports sixteen bit integer values, hence where a decimal point is used in the drive parameter, the register value will be
multiplied by a factor of ten,
E.g. Read Value of P1-01 = 500, therefore this is 50.0Hz.
For further details on communicating with the drive using Modbus RTU, please refer to your local Sales Partner.