Manual

7230 Hollister Avenue, Goleta, California 93117 | Tel: 805-968-0782 | Fax: 805-968-3154 | www.beisensors.com
9
Specication No.: 02135 Rev: 5-23-2013
PHD User Manual
7. Dene four additional parameters for the part:
Hysteresis– The Hysteresis option allows you to to
independently program the amount of hysteresis each output
will have. A value of zero degrees will give the minimum amount
of hysteresis and 11 degrees will give the maximum amount of
hysteresis. This value is most commonly set to zero.
Travel (Deg)– The Travel option allows you to program the
rotational angle you want to resolve. Values from 1° to 360° are
valid, however the linearity of the output may be negatively impacted for angles less than
15°. It is possible to program a separate angle for each of the sensor’s outputs; however
a slightly different programming sequence from this example is required.
Clamp Low and Clamp High– Allows you to independently set min/max percentage
limits for each output. These limits restrict each output from going beyond the limit
programmed. Clamp High and Low work exactly the same way for the Non-Ratio Metric
and PWM units as it does for the Ratiometric. For example assuming 5VDC is supplied to
the sensor’s input, the output would be as follows:
Clamp Low
(%)
Clamp High
(%)
Min/Max Vout
(V)
0 100 0/5
5 95 0.25/4.75
10 90 0.5/4.5
25 80 1.25/4
8. If PWM was selected as the Output Type two additional parameters must be set:
PWM Frequency is the output frequency which the PWM unit will output
at, this value is CONSTANT and does not change with output location.
PWM Polarity determines how the Duty Cycle
changes based on the position of the shaft.
Rising Edge– 0% High at 0% position, 100% High at
100% position.
Falling Edge– 0% High at 0% position, 100% High at
100% position.