2 Installation
The Absolute Encoder is connected with 3 M12
connectors..
2.1 Settings in the connection cap
2.1.1 Station address
The station (node) address is set by using the 8
DIP switches .The DIP n°8 is not used. Possible
addresses are between 0 and 126. Each
address can only be used once in the
network. The station address is read in when
switching on the power supply. An address
change by the Master (“Set_Slave_Add“) is
not supported by the version with DIP switches.
The address is coded with binary format:
OFF=0 ON=1, DIP8=OFF
Address Dip 1
Dip 2
Dip 3
Dip 4
Dip 5
Dip 6
Dip 7
Dip 8
0 OFF OFF OFF OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF OFF
...
124 OFF OFF ON ON ON ON ON OFF
125 ON OFF ON ON ON ON ON OFF
ON ON
Bus termination Address
2.1.2 Bus termination
If the encoder is connected at the end or
beginning of the bus line the termination
resistor must be switched on with DIP switches
n°1 et n°2.
Note
If the encoder must be changed during
operation, a separate active bus termination
should be used.