User guide

In order to replace the encoder later without a new
Teach-In procedure, the total measuring range
determined with the Teach-In should be transferred
into the system configuration. For this the „total
resolution“ must be entered into the parameter field
„desired measuring units“ (cp. 5.1.2) and the
referenc
e (cp. 5.1.3) must be set to “maximum total
measuring range“. When setting the parameters it
should be observed that the code sequence is
correct (the setting of the counting direction in
commissioning mode has to be transferred to the
system configuration). Subsequently the
commissioning mode can be switched off and the
encoder can be used in normal mode.
5.3.4 Preset value
T
he preset function is similar to the procedure
described in section 4.2.2. There is only one
differenc
e: When using the manufacturer-specific
versions 2.1 or 2.2 there is an acknowledgement
(bit 31 in the input double word is set to 1):
Status bits Data bits
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Master
MHM5
1 0 0 0 0 0 0 Transfer of the required position value (= preset value)
MHM5
Master
1 0 0 0 0 0 1 New = required position value is transferred
Master
MHM5
0 0 0 0 0 0 0 Reset bit 31 – normal mode
MHM5
Master
0 0 0 0 0 0 1 New = required position value is transferred
Page 26 BEI Sensors Profibus Manual serie M Revision 03/10