Safety Barrier Manual
7230 Hollister Avenue | Goleta, CA | 93117
Tel: 805.968.0782 / 800.960.2726
www.beisensors.com
Rev 2-20-14
Page 2/2
Intrinsic Safety Barrier
Specication No.: 02125-004
These commodities, technology or software if exported from the United States must be in accordance
with the Bureau of Industry, and Security, Export Administration regulations. Diversion contrary to U.S.
law is prohibited.
Specications
POWER SUPPLY / OUTPUT TYPE
Part Number Barrier Supply: Vs ±5% Output logic to Non-hazardous Area Apparatus
60004-002
12-28 VDC
Vout = 5V
Line Driver
up to 100 mA source/sink
(TTL & RS422 compatible)
60004-003 Vout = Vin
Line Driver
up to 100 mA source/sink
60004-004
Open
Collector
NPN
up to 80 mA sink
60004-005 Vout = 5V
Line Driver
up to 100 mA source/sink
Open wire detect option
60004-006 Vout = Vin
Line Driver
up to 100 mA source/sink
Open wire detect option
Caution: Operation above or below barrier supply voltage (Vs) range noted will cause permanent damage to barrier
!
BARRIER PARAMETERS
Class I, Gp D
Class II, Gps E,F,G
Group IIA
Class I, Gps C,D
Class II, Gps E,F,G
Group IIB
Class I, Gps A,B,C,D
Class II, Gps E,F,G
Group IIC
Barrier Output
(Po)
Voc (Uo) Isc (Io) Ca (Co) La (Lo) L/R Ratio Ca (Co) La (Lo) L/R Ratio Ca (Co) La (Lo) L/R Ratio
870 mW 9.48 VDC 367 mA 255 uF 2.1 mH 327 uH/Ω 27 uF 1.05 mH 160 uH/Ω 3.7 uF 0.26 mH 40.8 uH/Ω
INPUT TO BARRIER FROM ENCODER
Signals A, B, Z, A/, B/, Z/ differential or A,B,Z single-ended
Input Signal Impedance 500 Ω nominal (A to A/, B to B/, Z to Z/)
Input Signal level 4 VDC minimum, 6 VDC maximum
General Wiring Diagram (See BEI Sensors drawing 08067-003 for important details)