Phau Ntawv Qhia

Table Of Contents
PA13*A, PA14NC, PA15NC, PA16N*: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
Start-Up
Follow these steps to properly start up system:
1. After system is evacuated, fully open liquid and vapor service
valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps
installed. Replace stem caps after system is opened to refrigerant
flow. Replace caps finger-tight and tighten with wrench an
additional 1/12 turn.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set point is
below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or AUTO
mode, as desired. Operate unit for 15 minutes. Check system
refrigerant charge.
3-Phase Monitor
In 3-phase units a small circuit board is factory installed to monitor line
voltage. A small led will flash if a phase problem exists. See code
descriptions on monitor. If LED is flashing, disconnect power to unit
and interchange 2 field-wiring leads on unit contactor.
A00010
Fig. 7 – 3-Phase Monitor Control
(Applies to 3-Phase Units Only)
Sequence of Operation
Turn on power to indoor and outdoor units. Transformer is energized.
On a call for cooling, thermostat makes circuits R-Y and R-G. Circuit
R-Y energizes contactor, starting outdoor fan motor and compressor
circuit. R-G energizes indoor unit blower relay, starting indoor blower
motor on high speed.
When thermostat is satisfied, its contacts open, de-energizing contactor
and blower relay. Compressor and motors stop.
If indoor unit is equipped with a time-delay relay circuit, the indoor
blower will run an additional 90 seconds to increase system efficiency.
Check Charge
Factory charge amount and desired subcooling are shown on unit rating
plate. Charging method is shown on information plate inside unit. To
properly check or adjust charge, conditions must be favorable for
subcooling charging. Favorable conditions exist when the outdoor
temperature is between 70°F and 100°F (21.11°C and 37.78°C), and the
indoor temperature is between 70°F and 80°F (21.11°C and 26.67°C).
Follow the procedure below:
Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or
below 15 ft. (4.57 m) respectively.
NOTE: For 15 ft. (4.57 m) line set charge, refer to
Table 6 and Table 7
Some unit tonnages may require additional charge depending on size.
Find model tonnage size in table, reference factory charge versus
required charge to determine if additional charge is required. Additional
charge will be needed for line sets longer than 15 ft. (4.57 m).
For standard refrigerant line lengths (80 ft/24.38 m or less), allow system
to operate in cooling mode at least 15 minutes. If conditions are
favorable, check system charge by subcooling method. If any adjustment
is necessary, adjust charge slowly and allow system to operate for 15
minutes to stabilize before declaring a properly charged system.
If the indoor temperature is above 80°F (26.67°C), and the outdoor
temperature is in the favorable range, adjust system charge by weight
based on line length and allow the indoor temperature to drop to 80°F
(26.67°C) before attempting to check system charge by subcooling
method as described above.
If the indoor temperature is below 70°F (21.11°C), or the outdoor
temperature is not in the favorable range, adjust charge for line set length
above or below 15 ft. (4.57 m) only. Charge level should then be
appropriate for the system to achieve rated capacity. The charge level
could then be checked at another time when the both indoor and outdoor
temperatures are in a more favorable range.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than 35 ft
(10.7 m) vertical separation, See Long Line Guideline for special
charging requirements.
CAUTION
!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury, equipment
damage or improper operation.
S Do not overcharge system with refrigerant.
S Do not operate unit in a vacuum or at negative pressure.
S Compressor dome temperatures may be hot.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling
refrigerant and observe the following:
S Front seating service valves are equipped with Schrader valves.
Table 5 – Three-Phase Monitor LED Indicator
LED STATUS
OFF No call for compressor operation
FLASHING Reversed phase
ON Normal
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Ensure compressor rotation is correct.
3-phase scroll compressors are rotation sensitive.
A flash LED on phase monitor indicates reverse rotation. (See
Table 5)
This will not allow contractor to be energized.
Disconnect power to unit and interchange 2 field-wiring leads on unit
contactor.