Tus neeg siv phau ntawv

Table Of Contents
AGATWNDTE01C: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
condensate/inducer housing tubing pressure switch tubing venting
and electrical connections.
16. Go to Connect Electrical Components.
Horizontal, Suspended Installation for
Non-Condensing Furnaces
1. Furnaces may be suspended using two (2) pieces of 1-1/2-in. x
1-1/2-in. x 1/4-in. thick cold rolled angle iron underneath each
furnace and four (4) 3/8-in. (10 mm) diameter threaded rods. (See
Fig. 13)
2. Allow for at least 9 inches (228 mm) in front of each door for door
removal.
3. Each piece of angle iron must be secured to the bottom of each
furnace with at least two (2) No. 8 x 3/4-in. (19 mm) sheet metal
screws.
4. Maintain all clearances to combustibles per the furnace Installation,
Start-up and Operating Instructions.
5. Unistrut or similar material may be used, provided that the furnaces
do not sag in the middle or bend or twist at the support ends. The
support material must be secured to the bottom of each furnace in a
manner similar to securing angle iron to the furnace.
6. For all horizontal applications: Return air can only be connected to
bottom opening of furnace. A common return air plenum is
required for proper auxiliary limit switch operation.
7. Apply two factory-supplied foam strips to the back of each furnace.
Locate strips equal distance from top and bottom as shown in
Fig. 6. Trim off excess material.
8. Determine which side of furnace will be used to route external
extension harness. Remove 7/8-in. diameter accessory hole
knockouts in blower compartment side selected to attach harness to.
(See
Fig. 1)
9. Position furnaces back-to-back on attic platform or suspended
supports. Adjust and shim each furnace to align both furnaces.
Follow all clearance to combustible material.
NOTE: DO NOT lay furnace down flat on the side that external
extension harness is installed. Raise furnace up a minimum of 1-1/2
inches (38 mm) above deck so harness does not rub on casing or deck.
10. If furnaces are installed closer than 12 inches above a deck made
from combustible material, provide rollout protection as shown in
the furnace installation instructions. The bottom closure pan may be
used for this purpose.
11. Drill two 1/8-in. holes, approximately 1 in. (25 mm) below
discharge flange, from inside top of discharge opening and through
both furnaces. (See
Fig. 7) Drill two 1/8-in. holes, approximately 1
in. (25 mm) below return air flange, from inside top of return air
opening and through both furnaces. (Use
Fig. 8 as an example).
12. Drive one factory-supplied No. 6 x 3/4-in. LG screw through each
hole and tighten until furnaces are secure and foam strips have
sealed gap between furnaces.
13. Connect return- and supply-air ducts to furnaces. Seal duct
connections to prevent air leakage.
14. Move 115V junction box JB in either furnace from left-hand side to
right-hand side if required. Refer to furnace installation instructions
for complete details.
15. Go to Connect Electrical Components.
Representative drawing only, some models may vary.
L11F105
Fig. 9 – Attic Installation of Furnace for Condensing Furnace ONLY
NOTE: Rollout protection required.
Install 12” x 22” (304 x 559 mm) sheet metal in front of and above the
burner compartment area. The sheet metal MUST extend above the
furnace casing by 1-in. (25 mm with the door removed. A 1-in. (25 mm)
clearance minimum between top of furnace and combustible material is
required. The entire length of furnace must be supported when furnace is
used in horizontal position to ensure proper drainage
Representative drawing only, some models may vary.
A190218
Fig. 10 – Attic Installation of Back-to-Back Furnace
for Non-Condensing Furnace ONLY
Representative drawing only, some models may vary.
A190217
Fig. 11 – Attic Installation of Horizontal Furnace Stacked Together
for Non-Condensing Furnaces ONLY.
NOTE: Rollout protection required.
Install 12” x 22” (304 x 559 mm) sheet metal in front of burner
compartment area.
WARNING
!
UNIT DAMAGE AND FIRE HAZARD
Failure to follow this warning could result in unit damage, fire, personal
injury or death.
DO NOT use the back or side of the furnace for return-air duct
connections as limit cycling will occur.
TWINNING KIT EXTENSION HARNESS
VE N T
COMMON RETURN
VE N T
COMBUSTION AIR INTAKE
COMBUSTION AIR INTAKE
MANUAL SHUTOFF GAS
VA L V E
MANUAL SHUTOFF GAS
VALVE
SEDIMENT TRAP
SEDIMENT TRAP
SHEET METAL
4--3/4”
1”
30”
22”
12”
WORK PLATFORM