Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
Some sizes are not available for all models shown.
DESCRIPTION AND USAGE
IMPORTANT: Only the furnace sizes listed in
Table 2 or Table 3 can be
twinned with this kit. Both furnaces must have the same product number,
including heating and cooling sizes, to achieve correct operation. One
furnace is the Main furnace and the other furnace is the Secondary
furnace. The Main furnace controls the operation of the Secondary
furnace. All control connections are made to the Main furnace and Main
furnace wiring harness.
Twinned furnaces in these instructions are also referred to as the
left-hand furnace (LH) and right hand furnace (RH) or back-to-back.
NOTE: To determine referencing of Left Hand (LH) and Right Hand
(RH) furnace:
a. In the Side-by-Side, upflow and downflow applications,
reference the furnaces from the front, as you would see them in
the upflow application. (See
Fig. 2 and Fig. 3) The LH furnace is
the Main furnace and the RH furnace is the Secondary furnace.
b. In the Back-to-Back, upflow, downflow and horizontal
applications, reference the furnaces from the side of the external
extension harness. The LH furnace is the Main furnace and the
RH furnace is the Secondary furnace, as you would see them in
the upflow application. (See
Fig. 1 and Fig. 3)
Kit contents are shown in
Table 1.
NOTE: Refer to the Installation, Start-Up, and Operating Instructions
supplied with each furnace for information on venting, clearances,
start-up, maintenance, and other information not covered in this
publication.
A190244
Fig. 1 – External Extension
Non-Condensing Furnaces
Single Stage PSC
N8MS(N/L) 58ST(A/X) 58DL(A/X) 310(A/J)AV 311(A/J)AV PG8(M/J)AA WFM(R/L) R8MS(N/L)
451408 045--08 045--08 024045 024045 024045 045A024
451412 045--12 045--12 036045 036045 036045 045A036 451412
701408 070--08 070--08 024070 024070 024070 070A024
701412 070--12 070--12 036070 036070 036070 070A036 701412
701716 070--16 070--16 048070 048070 048070
901714 090--14 090--14 042090 042090 042090 090B042
902116 090--16 090--16 048090 048090 048090 090C048
902120 090--20 090--20 060090 060090 060090 902120
1101712 110--12 110--12 036110 036110 036110
1102116 110--16 110--16 048110 048110 048110 110C048
1102122 110--22 110--22 066110 066110 066110 110C066 1102122
1352116 135--16 135--16 048135 048135 048135
1352422 135--22 135--22 066135 066135 066135 135D066
1552420 155--20 155--20 060155 060155 060155
Single Stage FCT ECM
58SC(0/1) 58SB(0/1) 81(0/1)S 80(0/1)S PG80ES(A/L) N80ES(N/L) WFE(R/L) R80ES(N/L)
70E21--16 70E21--16 48070E21 48070E21 48070C 0702116 070C48 0702116
90E21--16 90E21--16 48090E21 48090E21 48090C 0902116 090C48 0902116
90E21--20 90E21--20 60090E21 60090E21 60090C 0902120 090C60 0902120
90E24--20 90E24--20 60090E24 60090E24 60090D 0902420 090D60 0902420
110E21--20 110E21--20 60110E21 60110E21 60110C 1102120 110C60 1102120
110E24--20 110E24--20 60110E24 60110E24 60110D 1102420 110D60 1102420
135E24--20 135E24--20 60135E24 60135E24 60135D 1352420 135D60 1352420
155E24--20 60155E24 60155D 1552420
Two Stage PSC
(F/G)8MTL (F/G)8MTL 58CT(A/X) 58CT(A/X) 312(A/J)AV 312(A/J)AV
451408 0902120 045-08 090--20 024045 060090
451412 1101712 045-12 110--12 036045 036110
701408 1102116 070-08 110--16 024070 048110
701412 1102122 070-12 110--22 036070 066110
701716 1352116 070-16 135--16 048070 048135
901714 1352422 090-14 135--22 042090 066135
902116 1552420 090-16 155--20 048090 060155
WARNING
!
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in unit and property damage.
A non-condensing furnace shall NOT be twinned with a condensing
furnace. Two-stage condensing or non-condensing furnaces shall not be
twinned with any single-stage furnace. Do not twin furnaces that have a
different number of blower motor speed taps together. Furnaces shall
only be twinned in the positions shown. Furnaces with variable-speed
constant airflow motors (VCA) furnaces shall not be twinned.
EXTERNAL EXTENSION
UNUSED 7/8 in. (22 mm) KNOCKOUTS