AGATWNDTE01C: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
VENTING
Refer to Installation, Start-Up, and Operating Instructions supplied with
each furnace for venting information. Each furnace must always be
individually vented. Do not common-vent or breach-vent condensing
furnaces. For allowable vent installations refer to furnace installation
instructions for allowable configurations and proper termination. It is
important that vent terminations be made as shown to avoid recirculation
of flue gases.
GAS SUPPLY PIPING
All gas connections must be made through exposed outer side of each
furnace. Do not common connect any connection other than supply and
return-air ducts. Furnaces are recommended to be provided with a single
shutoff valve. However, individual shutoff valves may be required by
local codes or jurisdictions. Refer to Installation, Start-Up, and
Operating Instructions provided with each furnace for additional gas
supply information.
CONDENSATE DRAIN CONNECTIONS
For condensing furnaces, the condensate trap is factory installed in the
furnace vestibule and factory connected for UPFLOW applications.
Install condensate trap such that field drain connections are on the left
side for LH (MAIN) furnace and on right side for RH (SECONDARY)
furnace.
The condensate trap must be relocated for downflow and horizontal
applications.
See furnace Installation, Start-Up, and Operating Instructions for details
on relocating the condensate and attaching field drain connections.
START-UP AND ADJUSTMENT
NOTE: Refer to Installation, Start-Up, and Operating Instructions
supplied with furnace for detailed information.
1. Shut off all power and gas to both furnaces.
2. For control boards with display and push-buttons, set the twinning
menu item on the Secondary Furnace to SEC as shown on wiring
label. For two-stage furnaces, also set the heating thermostat type
(HTT) as shown on wiring label.
NOTE: The secondary furnace blower will not run with cooling if this is
not set correctly
3. Set the heating blower speed to the same setting or tap on both
furnaces. Repeat for cooling and continuous fan speed settings.
4. Attach twinning connection wiring label above the existing furnace
wiring label on the inside of the LH furnace blower door. Use the
following labels for the following applications:
Single-Stage furnaces with single-stage thermostat, 347781-101
Single-Stage furnaces with two-stage thermostat, 347780-101
Two-Stage furnaces with single-stage or two-stage thermostat,
348927–101
Y1
Y/Y2
(Y on standard control board)
Energizes accessory cooling relay to start LH and A/C for first stage cooling and cooling speed blower
Y2 None Thermostat Y2 wired directly to RH accessory relay to start RH and A/C for second stage cooling
G G Starts both indoor fans on continuous fan speed
Dehum
*
Dehum
*
Reduces airflow in cooling mode when Dehum input is removed. See furnace manual for specifics.
*. Dehum is not available on all thermostats or control boards
Table 5 – Two-Stage Furnace Thermostat Connections
Two-Stage Heating with Single-Stage Thermostat Using Two-Stage Furnaces
THERMOSTAT
CONNECTIONS
CONTROL BOARD
CONNECTION
ACTION
C C Transformer Common
R R Power from control board to thermostat
W W/W1 Starts LH and RH furnaces in low heat or high heat, as determined by LH furnace control board*
Y 1 Y/Y2 Energizes accessory cooling relay to start both A/C units for cooling
Y2 None Thermostat Y2 wired directly to RH accessory relay to start RH and A/C for second stage cooling
G G Starts both indoor fans on continuous fan speed
Dehum
*
*. Do not remove ACRDJ from furnace control boards
Dehum
†. Dehum is not available on all thermostats or control boards
LHT switches must be in correct configuration
Reduces airflow in cooling mode when Dehum input is removed. See furnace manual for specifics.
Two-Stage Heating with Two-Stage Thermostat Using Two-Stage Furnaces
C C Transformer Common
R R Power from control board to thermostat
W1 W/W1 Starts both furnaces in low heat for first stage heating*
W2 W2 Starts both furnaces in high heat for second stage heating*
Y 1 Y/Y2 Energizes accessory cooling relay to start both A/C units for cooling
Y2 None Thermostat Y2 wired directly to RH accessory relay to start RH and A/C for second stage cooling
G G Starts both indoor fans on continuous fan speed
Dehum
*
Dehum
Reduces airflow in cooling mode when Dehum input is removed. See furnace manual for specifics.
Table 4 – Single-Stage Thermostat Connections (Continued)
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death,
or property damage.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position and install a lockout tag.
There may be more than one disconnect switch. Check accessories and
cooling unit for additional electrical supplies that must be shut off
during furnace servicing. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.