Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
THERMOSTAT CONNECTIONS
NOTE: All thermostat connections MUST be made at the Main furnace
control board. Do not make any thermostat connections to the Secondary
furnace control board.
Single-Stage Furnaces with Single-Stage Thermostat
(Field Supplied)
See Fig. 20 and Table 4
NOTE: This application allows both furnaces to operate together as a
single unit. See furnace Installation, Start-Up, and Operating Instructions
for further details on this heating mode.
1. Connect thermostat W lead to “W” on the Main furnace control
board.
2. Connect thermostat Y lead to Y or Y/Y2” on the Main furnace
control board.
3. Connect the G thermostat lead to the “G” terminal on the Main
furnace control board.
4. Connect thermostat R lead to “R” terminal on Main furnace control.
5. Connect thermostat C or COM lead to the “COM/24V” terminal on
the Main furnace control board.
Single-Stage Furnaces and A/C with Two-Stage
thermostat (Field Supplied)
See Fig. 21 and Table 4
NOTE: This application allows single-stage furnaces to operate with
one furnace or with both furnaces as determined by a two-stage
thermostat.
1. Connect thermostat W1 lead to “W” on the Main furnace control
board.
2. Connect thermostat W2 lead to White wire labeled “W” on the
twinning kit relay (TKR).
3. Connect first stage cooling thermostat lead Y1 to “Y or Y/Y2” on
the Main furnace control board.
4. Connect the second stage cooling thermostat lead Y/Y2 to the pilot
duty relay coil for the second stage contactor.
5. Connect the G thermostat lead to the “G” terminal on the Main
furnace control board.
6. Connect thermostat R lead to “R” terminal on Main furnace control.
7. Connect thermostat C or COM lead to the “COM/24V” terminal on
the Main furnace control board.
8. Connect the G thermostat lead to the “G” terminal on the Main
furnace control board.
9. Connect thermostat R lead to “R” terminal on Main furnace control.
10. Connect thermostat C or COM lead to the “COM/24V” terminal
on the Main furnace control board.
A210187
Fig. 20 – Single-Stage Furnace with Single-Stage Thermostat
A210188
Fig. 21 – Single-Stage Furnaces with Two-Stage Thermostat
WARNING
!
UNIT DAMAGE AND FIRE HAZARD
Failure to follow this warning could result in fire, personal injury or
death.
Make no connections between the R 24-VAC connector in one furnace
and the R 24-VAC connector in other furnace.