CONNECT ELECTRICAL COMPONENTS -
COOLING
NOTE: Cooling units used with twinned furnaces MUST be
single-stage A/C units. HEAT PUMPS CANNOT BE TWINNED with
gas furnaces.
When installing twinned outdoor units with twinned gas furnaces, it is
necessary to use field-supplied 24-VAC pilot-duty relay(s) and a
field-supplied 24-VAC/115-VAC transformer as shown in the individual
wiring diagrams to prevent overloading furnace 24-VAC/115-VAC
transformer. Transformer VA rating must be able to handle the load
imposed on it by the outdoor unit contactor(s).
1. Connect the L1 lead of the field-supplied transformer line voltage
lead to L1 on Main furnace control board.
2. Connect the Neutral lead of the field-supplied transformer to an
open Neutral terminal on the Main furnace control board.
NOTE: If sufficient room is available in the control box of the outdoor
unit, a 24-VAC/240-VAC transformer may be used. Connect line voltage
leads of the transformer to the appropriate connection locations on the
outdoor unit, Refer to the outdoor unit wiring diagram for specific
details.
For Single-Stage A/C Operation with Single-Stage
Thermostat
See Fig. 20.
In the configuration both A/C units come on together as a single unit. It
will be necessary to supply one pilot duty relay for A/C operation.
1. Connect one coil terminal of the field-supplied pilot duty relay to
the “COM/24V” terminal of the furnace control board.
2. Connect the other coil terminal of the field-supplied pilot duty relay
to the “Y or Y/Y2” terminal of the furnace control board.
3. Connect the R terminal of the field-supplied transformer to the open
contract of the pilot duty relay.
4. Connect the other open contact to the wire for Y terminal of the
contactor(s).
5. Connect the Common terminal of the contactor(s) to the C terminal
of the field supplied transformer.
For Two-Stage A/C Operation with a Two-Stage
thermostat.
See Fig. 21.
In this configuration, the individual A/C unit(s) are staged on and run as
controlled by the two-stage thermostat. It will be necessary to supply
two pilot duty relays for staged A/C operation. Once A/C unit will be the
first stage unit, the other A/C unit will be the second stage unit.
Single-stage furnaces are staged individually by the thermostat.
1. Connect one coil terminal of each of the pilot duty relay together.
2. Connect these two terminals to the “COM/24V” terminal of the
furnace control board.
3. Select one of the relays to be the relay for first stage cooling.
Connect the coil terminal of this relay to the “Y or Y/Y2” terminal
of the furnace control board.
4. The other relay is the second stage cooling relay. The coil terminal
of this relay will connect to the “Y/Y2” terminal of the thermostat.
Do not connect the terminal to the Y1 terminal on the furnace
control board.
5. Connect the R terminal of the field-supplied transformer to the open
contract of each pilot duty relay.
6. Connect the other open contact of the first stage cooling relay to the
wire for Y terminal of the first stage contactor.
7. Connect the other open contact of the first stage cooling relay to the
wire for Y terminal of the second stage contactor.
8. Connect the Common terminal of the contactor(s) to the C terminal
of the field supplied transformer.
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death,
or property damage.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position and install a lockout tag.
There may be more than one disconnect switch. Check accessories and
cooling unit for additional electrical supplies that must be shut off
during furnace servicing. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
PLUG
LABEL
BLUE WIRE ASSY.
RED WIRE ASSY.
RELAY
ORANGE WIRE ASSY.
ORANGE WIRE ASSY.
BLACK WIRE ASSY.
PLUG
WIRE TIE
YELLOW WIRE ASSY.
BLACK WIRE ASSY.
RED WIRE
WHITE WIRE ASSY.
R SECONDARY
W SECONDARY
C SECONDARY
TEST SECONDARY
ORANGE
BLUE
RED
RELAY
BLACK
SCREW
(2) REQ’D
AUXILLARY LIMIT
BRACKET
ASSY
C
3
1
2
4
SEC--1
/COM
C
SEC--1
/COM
SECONDARY