Datasheet

www.Beha-Amprobe.com
©2015 Beha-Amprobe
®
13104--engBeha-Amprobe
®
| In den Engematten 14 | 79286 Glottertal, Germany | Tel: +49 (0) 7684 8009-0 | info@beha-amprobe.de | www.Beha-Amprobe.com
Quick Guide
Features:
2100-Alpha 2100-Beta 2100-Gamma
Safety Rating
(overvoltage category)
CAT III 690 / CAT IV 600 CAT III 690 / CAT IV 600 CAT III 1000 / CAT IV 600
Voltage Range 12 - 690 V AC/DC 12 - 690 V AC/DC 6 - 1000 V AC / 6 - 1200 V DC
Voltage Indication - LCD 12 - 690 V AC/DC 6 - 1000 V AC, 6 - 1200 V DC
Voltage Indication - LED (12 - 690 V)
Continuity Test
(visual and audible indication)
RCD Trip Test (10 mA or 30 mA)
Single Pole Phase Test
Full Range Polarity Detection
Two Pole Phase Rotation Indication
Right Right Right/Left
IP 64 Splash and Dust Proof
Torch Light/Measurement
Area Illumination
Double Insulated Cable with
Wear Indication
4 mm Test Probe Extensions (screwable) and
Removable GS38 Protective Probe Caps
Data Hold Function
Resistance Measurement and Low
Resistance Indication
Non-Contact Voltage Detection
Test probe protector cover
with accessory storage
Store the 4 mm test probe extensions and
GS38 protective probe caps, ensuring you
always have them when needed. The test
probe protector cover tip also helps to
open UK electrical safety outlets.
Two Button Switchable Load/
RCD Trip Test
When the two buttons are not pressed the
unit is in high impedance mode, providing
additional safety protection when testing
live power sources, and avoiding accidental
tripping of residual-current devices/earth
leakage circuit breakers (RCD/ELCB).
When the buttons are pressed the unit
is in low impedance mode, eliminating
inaccurate readings as result of ghost
voltage. Additionally, in systems with RCDs
you can press the buttons to intentionally
trip 10 mA or 30 mA RCDs remotely and
determine if they are wired correctly.
Long, durable test leads with
wear indicator
Extra-long 1.5 m test leads make testing
fast and convenient. The two pole tester’s
rugged, durable test leads have two layers
of insulation for added durability and
safety. If the inner, contrasting-colored
layer is showing, that’s a sign that the test
leads require replacement.