DETAILED SPECIFICATIONS
AC Voltage Measurement L-N, L-PE , N-PE
Display range Resolution
Intrinsic accuracy
50Hz – 60hz
Measurement range Operating error Input impedance
Overload
protection
0 - 500V 0,1V ± (2% + 2D) 50 – 500Vac ± (3% + 3D) 3,3MΩ / 360 kΩ 600 Vrms
Continuity Measurement
Display range
(auto-ranging)
Resolution Intrinsic accuracy Measurement range Operating error Test current
Open circuit
voltage
0 - 20 Ω 0,01 Ω
± (3% + 3D) 0,30 - 2000 ± (10% + 3D)
> 200 mA for
Rlo < 2 Ohms
> 4V200 Ω 0,1 Ω
2000 Ω 1 Ω
Insulation Resistance Measurement
Test voltage Display range Resolution Test current
Intrinsic
accuracy
Measurement range
Operating
error
Accuracy of test voltage
at max. 1mA load
100 V
0 MΩ to 20 MΩ
20 MΩ to 100 MΩ
0,01 MΩ
0,1 MΩ
1 mA @ 100 kΩ
± (5% + 5 dgt.)
0,1 MΩ to 20 MΩ
20 MΩ to 200 MΩ
± (12% + 3D)
+20%, -0%
250 V
0 MΩ to 20 MΩ
20 MΩ to 200 MΩ
1 mA @ 250 kΩ
0,25 MΩ to 20 MΩ
20 MΩ to 200 MΩ
500 V
0 MΩ to 20 MΩ
20 MΩ to 200 MΩ
200 MΩ to 500 MΩ
0,01 MΩ
0,1 MΩ
1 MΩ
1 mA @ 500 kΩ
± (5% + 5 dgt.),
For R > 200 MΩ
±10%
0,5 MΩ to 20 MΩ
20 MΩ to 200 MΩ
200 MΩ to 500 MΩ
± (12% + 3D)
± (12% + 3D)
± (15% + 5D)
1000 V
0 MΩ to 200 MΩ
200 MΩ to 1000 MΩ
0,1 MΩ
1 MΩ
1 mA @ 1 MΩ
1 MΩ to 200 MΩ
200 MΩ to 1000 MΩ
± (12% + 3D)
± (15% + 5D)
Impedance Measurements
Display range
(auto-ranging)
Resolution Intrinsic accuracy Measurement range Operating error
0 - 20 Ω 0,01 Ω
± ( 4% + 5 dgt.) no trip*
± ( 3% + 3 dgt.) high current
Notripmode 0,50 – 2000 Ω ± (15% + 8D) *
200 Ω 0,1 Ω ± 5% Hicurrentmode 0,30 – 200 Ω ± (10% + 5D)
2000 Ω 1 Ω ± 6% * Valid for resistance of neutral circuit < 20 Ohms
PSC Test
Computation PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance.
Range 0 – 10 kA
ResolutionandUnits I
K
< 1000 A; 1 A / I
K
> 1000 A; 0,1 A
Accuracy Determined by accuracy of Loop Resistance and Mains Voltage measurements.
RCD Testing
Types of RCDs tested
RCDType
ProInstall-100-D ProInstall-200-D
AC(RespondstoAC)*
A(Respondstopulsedsignal)
G(General,nodelay)
S(Timedelayed)
AC G
■ ■
AC S
■ ■
A G
■ ■
A S
■ ■
B G
■
B S
■
*1000mA for type AC only Voltage range: 100 … 264 VAC