Manual
13/16 CC1B-Hints-en Preliminary 04.02.2003 HVAC Products
3. Notes
3.2 Your record of values
RWF40 Setpoint Your
Man. Ref. Display Setting
Configuration level items ( Sec 6.4 )
Range Factory
S
ec 8.1
C111
Analog input 1, 2 and 3;D2 setpoint changeover / shift N /A 9030
S
ec 8.1 / 8.2
C112
Limit comparator; controller type; setpoint 1; locking N /A 0010
S
ec 8.1
C113
Unit address; decimal place / unit, signal for out-of-range N /A 0110
S
ec 8.3.1
SCL
SCale Low, analog input 1, measured value range -1999 to +9999 0
S
ec 8.3.2
SCH
SCale High, analog input 1, measured value range -1999 to +9999 100
S
ec 8.3.3
SCL2
SCale Low, analog input 2, measured value range -1999 to +9999 0
S
ec 8.3.4
SCH2
SCale High, analog input 2, measured value range -1999 to +9999 100
S
ec 8.3.5
SPL
Set Point Low limit -1999 to +9999 0
S
ec 8.3.6
SPH
Set Point High limit -1999 to +9999 100
S
ec 8.3.7
OFF1
OFFset analog input 1, Actual value correction -1999 to +9999 0
S
ec 8.3.8
OFF2
OFFset analog input 2, Actual value correction -1999 to +9999 0
S
ec 8.3.9
OFF3
OFFset analog input 3, Actual value correction -1999 to +9999 0
S
ec 8.3.10
dF1
digital Filter, analog input 1, 2
nd
order, in seconds 0 to 100 1
Setpoint Your
Display Setting
Configuration level items, Modbus option (only RW F40.0X2B97) ( Sec 6.4 )
Range Factory
S
ec 8.3.11
dF3
Filter time constant, digital Filter, analog input 3 weather-dependent setpoint shift 0 to 1440 1278
S
ec 8.3.12
oLLo
Working range, Limit Lower
-1999 to +9999
-1999
S
ec 8.3.13
oLHi
Working range, Limit High
-1999 to +9999
9999
S
ec 8.3.14
Dtt
Bus watchDog timer (in seconds) 0 to 7200 30
Setpoint Your
Display Setting
Parameter level items ( Sec 6.3 )
Range Factory
S
ec 7 / 8.2
AL
Alarm value for K6 Limit comparator (alarm programmable relay) -1999 to +9999 0
S
ec 7 / 8.2
HYSt
Hysteresis, (switching differential) for K6 limit comparator 0 to 999.9 1
S
ec 7 / 8.2
Pb.1
Proportional band 1 (affects P-response of controller) 0.1 to 999.9 10
S
ec 7 / 8.2
dt
derivative time (in seconds) (affects D-response of controller) 0 to 9999 80
S
ec 7 / 8.2
rt
Integral action time (in seconds) , (affects I-response of controller) 0 to 9999 350
S
ec 7 / 8.2
db *
dead band, contact spacing, * visible when C112 is xxx0, 3-pos modulating 0 to 999.9 1
S
ec 7 / 8.2
tt *
Actuator running time (in seconds) , * visible when C112 is xxx0, 3-pos modulating 10 to 3000 15
S
ec 7 / 5.51
HYS1
Switch-on threshold, HYSteresis 1, 2-stage burner 0 to -199.9 -5
S
ec 7 / 5.2
HYS2
Switch-off threshold, HYSteresis 2, 2-stage burner 0 to HYS3 3
S
ec 7 / 5.2
HYS3
Switch-off threshold, HYSteresis 3, upper 0 to 999.9 5
S
ec 7 / 5.6
q
Response threshold (Q) 0 to 999.9 0
S
ec 7 / 5.51
H
Heating curve slope 0 to 4 1
S
ec 7 / 5.5
P
Parallel displacement (weather dependent setpoint shift) -90 to +90 0
Setpoint Your
Display Setting
User level items ( Sec 6.2.1 )
Range Factory
S
ec 6.2.1
SP1
Set Point 1 SPL to SPH 0
S
ec 6.2.1
SP2
Set Point 2, digital input 2, D2=0 SPL to SPH 0
S
ec 6.2.1
dSP
digital Set Point shift, digital input 2, D2=1 SPL to SPH 0
S
ec 11.1.3
tA
temperature, Ambient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x --
S
ec 11.1.2
SP.E
Set Point External, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x SPL to SPH --