Boiler Guide
Basic Burner Setup Information Additional Information
Appliance
Model
Low Fire
Rate Baffle
Std. Air
Tube
Pump
Pressure
Recom.
Chassis
Approximate
Air Settings*
Insertion
Depth
Burner
Type
Head
Type
Static Plate/
Stop Screw
Nozzle
Type
Notes
Brock Engineering (cont’d)
CCC AFG F3 2-3/4” 0.65 X 80°W — AF65XN 100 B2007 — —
CCC AFG F3 2-3/4” 0.85 X 80°W — AF65XN 100 B2007 — —
IB-30 AFG F0 3-3/8” 0.60 X 80°W — AF65XR 100 B2007 — —
MBT AFG F3 2-3/4” 1.00 X 80°W — AF65XN 100 B2007 — —
MBT AFG F3 2-3/4” 0.85 X 80°W — AF65XN 100 B2007 — —
MBT AFG F3 2-3/4” 0.75 X 80°W — AF65XN 100 B2007 — —
MBT AFG F3 2-3/4” 0.65 X 80°W — AF65XN 100 B2007 — —
BDHF/BMF/
BHZF/BLF AFII 85 HLX6 # 3 0.50 X 60° W — HLX70HD 155 B7711 3 4 -15/16”
MBU SR F3 3-3/8” 0.85 X 70°AH — SR65ROSS 100 B1025 — 5-7/8” 27
MBU SR F3 3-3/8” 0.75 X 70°AH — SR65ROSS 100 B1025 — 5-7/8” 27
MBU SR F3 3-3/8” 0.65 X 70°AH — SR65ROSS 100 B1025 — 5-7/8” 27
(27) Requires Stainless Steel air tube.
Bryan Steam Corp.
D250 AF F12 2-3/4” 1.50 X 80°B — AF44XO 100 B3001 — —
D350 AF F22 2-3/4” 2.00 X 80°A — AF44XP 100 B3001 — —
250 CF375 SL1-1 — 1.50 X 60°ES — CF56KZ 140 BCF3907 S-10 / B-1 5"
350 CF375 SL1-3 — 2.00 X 60°P — CF56KZ 190 BCF3907 S-10 / B-2 5"
450 CF500 V1-4 — 2.50 X 45°P — CF100KK 150 BCF809 S-4 / B-0 5"
650 CF800 KH-3 — 4.00 X 60°B — CF100KH 140 BCF403 S-7 / B-0 5-1/2”
850 CF800 KJ-2 — 5.00 X 45°B — CF100KJ 150 BCF403 S-7 / B-0 5-1/2”
D450 SF F22 NONE 2.50 X 80°A — SF90NH 100 B711 — —
D650 SF F310 NONE 4.00 X 80°A — SF90FT 100 B711 — —
Bryant
361AAN036075 AFG F3 3-3/8” 0.50 X 70°H 5880 AF47YHFS 100 B2007 — — 1
361AAN036105 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2007 — — 1
361AAN048125 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2007 — — 1
361AAN060155 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2007 — — 1
362AAN036075 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2007 — — 1
362AAN036105 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2007 — — 1
362AAN048125 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2007 — — 1
362AAN060155 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2007 — — 1
367AAN105 AFG F3 3-3/8”R 0.65 X 70°B — AF53BN 130 B2007 S-8 / B-0 2-7/8”
367AAN120 AFG F3 2-3/4” 0.75 X 70°B — AF53XN 130 B2007 S-8 / B-1 2-7/8”
369AAN105 AFG F3 3-3/8”R 0.65 x 70°B — AF53BN 130 B2007 S-8 / B-0 2-7/8”
369AAN120 AFG F3 2-3/4” 0.75 X 70°B — AF53XN 130 B2007 S-8 / B-1 2-7/8”
OBM/OVM098 AFG L2 3-3/8” 0.50 X 60°A 5880 AFG70MQSS 150 B2007 S-6 / B-0 1-3/4”
OBM/OVM112 AFG L2 3-3/8” 0.60 X 60°W 5880 AFG70MQSS 140 B2007 S-10 / B-0 1-3/4”
OBM/OVM NX 6-slot — 0.60 X 60°A — NZ56LQ 135 B8001 2.5 1-3/4” 40
OBM/OVM NX 6-slot — 0.40 X 60°A 32229 NX56LQ 155 B8001 2 1-3/4” 40
OBM/OVM NX 6-slot — 0.50 X 60°W 32229 NX56LQ 145 B8001 2.75 1-3/4” 40
OBM/OVM154 NX 6-slot — 0.75 X 60°B — NX50LC 160 B8001 2.5 1-3/4”` 40
(1) “FS” on air tube combination = fiber heat shield on combustion head.
(40) Must maintain 0° downward pitch on air tube/flange.
Buderus
G-115-3 (21) AFG L2 2-3/4” 0.50 X 45°B (H) 5880 AFG90MPASN 150 B2007 S-9 / B-0 6-1/4” 9,16,31
G-115-4 (28) AFG L2 2-3/4” 0.65 X 60°B (H) — AFG90MPASN 150 B2007 S-8 / B-0 6-1/4” 9, 16, 31
G-115-5 (34) AFG L2 2-3/4” 0.85 X 60°B (H) — AFG90MPASN 140 B2007 S-10 / B-3 6-1/4” 9, 16, 31
G115-5 (34) AFII 150 AF2-9 # 2 0.85 X 60°B — HLX50HC 145 B7203 4 3” 40
G115-5 (34) AFII 150 AF2-9 # 2 0.85 X 45°B — HLX50HC 175 B7203 — 3” 40
22