Boiler Guide
Basic Burner Setup Information Additional Information
Appliance
Model
Low Fire
Rate Baffle
Std. Air
Tube
Pump
Pressure
Recom.
Chassis
Approximate
Air Settings*
Insertion
Depth
Burner
Type
Head
Type
Static Plate/
Stop Screw
Nozzle
Type
Notes
Heat Controller / ComfortAir / Century / Patriot (cont’d)
OUFB 125 AFG F4 3-3/8” 0.85 X 80°B — AF46WPHS 140 B2007 S-6 / B-0 5” 2
OUFB 125 AFG F4 3-3/8” 1.00 X 80°B — AF46WPHS 140 B2007 S-9 / B-0 5” 2
OUFB 75 AFG F0 2-3/4” 0.50 X 80°A 5880 AF46XZTHS 100 B2007 S-4 / B-0 5” 2, 58
OUFB 75 AFG F0 2-3/4” 0.65 X 80°B 5880 AF46XZTHS 100 B2007 S-10 / B-0 5” 2, 58
OUFB 95 AFG F3 2-3/4” 0.65 X 80°B 5880 AF46XNHS 140 B2007 S-6 / B-0 5” 2
OUFB 95 AFG F3 2-3/4” 0.75 X 80°B 5880 AF46XNHS 140 B2007 S-8 / B-0 5” 2
OHD 112 AG 2”ID 34-9 1.00 X 80°S — A60BC 100 B2007 — —
OHD 84 AG 2”ID 34-9 0.75 X 80°S — A60BC 100 B2007 — —
(2) “HS” on air tube combination = ceramic heat shield on combustion head.
(13) Requires blank air band.
(58) Requires 2-Slot Air Band #5151506.
Heat Transfer Products
OFT-50 AF F3 3-3/8” 0.75 X 80°A — AF65YHHSSS 100 B2007 S-4 / B-0 — 2, 27
HTP30C AFG F3 3-3/8” 0.65 X 80°B — AF65YHSS 100 B2007 S-7 / B-0 — 27
OFT-30B AFG F3 3-3/8” 0.65 X 80°B 5880 AF65YHHSSS 100 B2007 S-4 / B-0 — 2, 27
(2) “HS” on air tube combination = ceramic heat shield on combustion head.
(27) Requires Stainless Steel air tube.
Heil Quaker / Temp Star / ICP
NM05055BFA1 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2008 — — 1
NM05085BFA1 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NM05100BFA1 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NM05125BFA1 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2008 — — 1
(1) “FS” on air tube combination = fiber heat shield on combustion head.
Home Aire
XEF0112F070 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2008 — — 1
XEF0112F105 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2008 — — 1
XEF0116F125 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2008 — — 1
XEF0120F155 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2008 — — 1
(1) “FS” on air tube combination = fiber heat shield on combustion head.
HTO / ICP
NCO5055BFA1 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2008 — — 1
NCO5075BFA1 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NCO5100BHA1 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NCO5125BHA1 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2008 — — 1
NLO5055BFA1 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2008 — — 1
NLO5085BFA1 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NLO5100BHA1 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NLO5125BKA1 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2008 — — 1
NMO5055BFA1 AFG F3 3-3/8” 0.50 X 80°S 5880 AF47YHFS 100 B2008 — — 1
NMO5085BGA1 AFG F3 3-3/8” 0.75 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NMO5100BHA1 AFG F3 3-3/8” 0.90 X 70°H 5880 AF47YHFS 100 B2008 — — 1
NMO5125BKA1 AFG F6 2-3/4” 1.10 X 70°H 5880 AF67YBFS 100 B2008 — — 1
(1) “FS” on air tube combination = fiber heat shield on combustion head.
Hunter Comfort
HB115 AFII 85 AF2-9 # 6 0.75 X 60°B — HLX70HC 140 B7703 — —
HB115 AFII 85 AF2-9 # 5 0.65 X 60°B — HLX70HC 140 B7703 — —
HB115 AFII 85 AF2-9 # 3 0.60 X 60°B — HLX70HC 140 B7703 — —
51