Boiler Guide

Basic Burner Setup Information Additional Information
Appliance
Model
Low Fire
Rate Baffle
Std. Air
Tube
Pump
Pressure
Recom.
Chassis
Approximate
Air Settings*
Insertion
Depth
Burner
Type
Head
Type
Static Plate/
Stop Screw
Nozzle
Type
Notes
Burnham (contd)
V-78 AFG V1-5 2-3/4” 2.00 X 45°P (H) AFG50MD 140 B2007 S-10 / B-5 1-11/16” 31
V-79 AFG V1-6 2-3/4” 2.25 X 45°P (H) AFG50MD 140 B2007 S-10 / B-7 1-11/16” 31
V-82 AFG L1 3-3/8” 0.50 X 60°A AFG70MMASN 140 B2008 S-4 / B-0 2-1/16” 9,10,16
V-83 AFG L1 3-3/8” 0.85 X 60°A AFG70MMAQN 140 B2008 S-10 / B-2 1-11/16” 9,16,37
V-83S AFG L1 3-3/8” 0.60 X 60°A 5880 AFG70MMAQN 140 B2008 S-10 / B-1 1-11/16” 9,16,37
V-84 AFG V1-0 2-3/4” 1.10 X 60°B (H) AFG70MDAQN 140 B2008 S-10 / B-2 1-11/16”
9,31,37
V-84 AFG V1-0 2-3/4” 1.00 X 60°B (H) AFG70MDAQN 140 B2008 S-10 / B-1 1-11/16”
9,31,37
V-84S AFG V1-0 2-3/4” 0.85 X 60°A AFG70MDAQN 140 B2008 S-10 / B-3 1-11/16” 9,37
V-85 AFG V1-2 2-3/4” 1.35 X 60°B AFG70MDASN 140 B2008 S-10 / B-5 1-11/16” 9
V-85S AFG V1-0 2-3/4” 1.10 X 60°B AFG70MDASN 140 B2008 S-10 / B-1 1-11/16” 9
V-86 AFG V1-3 2-3/4” 1.50 X 45°B AFG70MDASN 160 B2008 S-10 / B-4 1-11/16” 9
V-86S AFG V1-2 2-3/4” 1.35 X 60°B AFG70MDASN 140 B2008 S-10 / B-3 1-11/16” 9
V-87 AFG V1-4 2-3/4” 1.65 X 45°B (H) AFG70MDASN 170 B2008 S-10 / B-3 1-11/16” 9, 31
V-88 AFG V1-4 2-3/4” 1.75 X 45°B (H) AFG70MDASN 170 B2008 S-10 / B-5 1-11/16” 9, 31
V-89 AFG V1-6 2-3/4” 2.00 X 45°P (H) AFG70MDASN 170 B2008 S-10 / B-7 1-11/16” 9, 31
V-8H2W AFG L1 3-3/8” 0.50 X 60°A AFG70MMASN 140 B2007 S-4 / B-7 2-1/16” 9, 16
V-8H3S AFG L1 3-3/8” 0.60 X 60°A 5880 AFG70MMAQN 140 B2007 S-10 / B-1 1-11/16” 9, 16
V-8H3W AFG L1 3-3/8” 0.85 X 60°A AFG70MMAQN 140 B2007 S-10 / B-2 1-11/16” 9, 16
V-8H4S AFG V1-0 2-3/4” 0.85 X 60°A AFG70MDAQN 140 B2007 S-10 / B-1 1-11/16” 9
V-8H4W AFG V1-0 2-3/4” 1.10 X 60°B (H) AFG70MDAQN 140 B2007 S-7 / B-1 1-11/16” 9, 31
V-8H5S AFG V1-0 2-3/4” 1.10 X 60°B AFG70MDASN 140 B2007 S-10 / B-1 1-11/16” 9
V-8H5W AFG V1-2 2-3/4” 1.35 X 60°B AFG70MDASN 140 B2007 S-10 / B-5 1-11/16” 9
V-8H6S AFG V1-2 2-3/4” 1.35 X 60°B AFG70MDASN 140 B2007 S-10 / B-3 1-11/16” 9
V-8H6W AFG V1-3 2-3/4” 1.50 X 45°B AFG70MDASN 160 B2007 S-10 / B-3 1-11/16” 9
V-8H7S AFG V1-4 2-3/4” 1.65 X 45°B AFG70MDASN 170 B2007 S-10 / B-3 1-11/16” 9
V-8H7W AFG V1-4 2-3/4” 1.65 X 45°B AFG70MDASN 170 B2007 S-10 / B-3 1-11/16” 9
V-8H8S AFG V1-4 2-3/4” 1.75 X 45°B AFG70MDASN 170 B2007 S-10 / B-5 1-11/16” 9
V-8H8W AFG V1-4 2-3/4” 1.75 X 45°B AFG70MDASN 170 B2007 S-10 / B-5 1-11/16” 9
V-8H9S AFG V1-6 2-3/4” 2.00 X 45°P AFG70MDASN 170 B2007 S-10 / B-7 1-11/16” 9
V-8H9W AFG V1-6 2-3/4” 2.00 X 45°P AFG70MDASN 170 B2007 S-10 / B-7 1-11/16” 9
LEDV1 AFII 85 AF2-6 # 2 0.50 X 70°B HLX50HD 140 B7711 2 2” 5,6,34
LEDV2 AFII 150 AF2-9 # 3 0.85 X 60°B HLX50HE 140 B7210 4 2” 5,6,34
LEDV3 AFII 150 AF2-9 # 5 1.00 X 60°B HLX50HE 140 B7210 4 2” 5,6,34
RS117 SF F220 2-3/4” 2.50 X 80°B SF60FY 100 B711
RS118 SF F220 2-3/4” 3.00 X 80°B SF60FY 100 B711
(5) Non-delay valve required.
(6) Nozzle line heater required.
(8) 2-slot air band 31840BK required.
(9) Electrode settings of 1/4” above center of nozzle, 1/8” in front of nozzle and gap 5/32”.
(10) 3-slot air shutter #32211.
(16) With conic shroud, “Z” dimension is 1-3/4”.
(27) Reqires Stainless Steel air tube.
(31) The (H) in the Nozzle Description denotes a Hago.
(34) Must maintain 3° downward pitch on air tube/flange.
(37) AQ in ATC designates 16-slot venturi.
(51) Burner specs before March 2013
(52) Burner specs after March 2013
25