Boiler Guide
Basic Burner Setup Information Additional Information
Appliance
Model
Low Fire
Rate Baffle
Std. Air
Tube
Pump
Pressure
Recom.
Chassis
Approximate
Air Settings*
Insertion
Depth
Burner
Type
Head
Type
Static Plate/
Stop Screw
Nozzle
Type
Notes
Cox Mfg. Inc.
CFO 115 AF F3 2-3/4” 1.00 X 80°B — AF90XN 100 B3001 — —
CFO 150 AF F3 2-3/4” 1.25 X 80°B — AF90XN 100 B3001 — —
CFO 225 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
CFO 80 AF F3 2-3/4” 0.75 X 80°B — AF90XN 100 B3001 — —
CFO 95 AF F3 2-3/4” 0.85 X 80°B — AF90XN 100 B3001 — —
HO 115 AF F3 2-3/4” 1.00 X 80°B — AF90XN 100 B3001 — —
HO 150 AF F3 2-3/4” 1.25 X 80°B — AF90XN 100 B3001 — —
HO 225 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
HO 80 AF F3 2-3/4” 0.75 X 80°B — AF90XN 100 B3001 — —
HO 95 AF F3 2-3/4” 0.85 X 80°B — AF90XN 100 B3001 — —
OD 115 AF F3 2-3/4” 1.00 X 80°B — AF90XN 100 B3001 — —
OD 150 AF F3 2-3/4” 1.25 X 80°B — AF90XN 100 B3001 — —
OD 225 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
OD 80 AF F3 2-3/4” 0.75 X 80°B — AF90XN 100 B3001 — —
OD 95 AF F3 2-3/4” 0.85 X 80°B — AF90XN 100 B3001 — —
RO 115 AF F3 2-3/4” 1.00 X 80°B — AF90XN 100 B3001 — —
RO 212 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
RO 225 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
RO 80 AF F3 2-3/4” 0.75 X 80°B — AF90XN 100 B3001 — —
RO 95 AF F3 2-3/4” 0.85 X 80°B — AF90XN 100 B3001 — —
SO 115 AF F3 2-3/4” 1.00 X 80°B — AF90XN 100 B3001 — —
SO 150 AF F3 2-3/4” 1.25 X 80°B — AF90XN 100 B3001 — —
SO 225 AF F12 2-3/4” 1.75 X 80°B — AF90XO 100 B3001 — —
SO 80 AF F3 2-3/4” 0.75 X 80°B — AF90XN 100 B3001 — —
SO 95 AF F3 2-3/4” 0.85 X 80°B — AF90XN 100 B3001 — —
CFO 1050 SF F310 NONE 2 - 4.50 X 80°B — SF90FT 100 B711 — — 30
CFO 300 SF F310 NONE 2.50 X 80°B — SF90FT 100 B711 — —
CFO 400 SF F310 NONE 3.50 X 80°B — SF90FT 100 B711 — —
CFO 525 SF F310 NONE 4.50 X 80°B — SF90FT 100 B711 — —
CFO 600 SF F310 NONE 2 - 2.50 X 80°B — SF90FT 100 B711 — — 30
CFO 800 SF F310 NONE 2 - 3.50 X 80°B — SF90FT 100 B711 — — 30
HO 1050 SF F310 NONE 2 - 4.50 X 80°B — SF90FT 100 B711 — — 30
HO 300 SF F310 NONE 2.50 X 80°B — SF90FT 100 B711 — —
HO 400 SF F310 NONE 3.50 X 80°B — SF90FT 100 B711 — —
HO 525 SF F310 NONE 4.50 X 80°B — SF90FT 100 B711 — —
HO 600 SF F310 NONE 2 - 2.50 X 80°B — SF90FT 100 B711 — — 30
HO 800 SF F310 NONE 2 - 3.50 X 80°B — SF90FT 100 B711 — — 30
OD 1050 SF F310 NONE 2 - 4.50 X 80°B — SF90FT 100 B711 — — 30
OD 300 SF F310 NONE 2.50 X 80°B — SF90FT 100 B711 — —
OD 400 SF F310 NONE 3.50 X 80°B — SF90FT 100 B711 — —
OD 525 SF F310 NONE 4.50 X 80°B — SF90FT 100 B711 — —
OD 600 SF F310 NONE 2 - 2.50 X 80°B — SF90FT 100 B711 — — 30
OD 800 SF F310 NONE 2 - 3.50 X 80°B — SF90FT 100 B711 — — 30
RO 1050 SF F310 NONE 2 - 4.50 X 80°B — SF90FT 100 B711 — — 30
RO 300 SF F310 NONE 2.50 X 80°B — SF90FT 100 B711 — —
RO 400 SF F310 NONE 3.50 X 80°B — SF90FT 100 B711 — —
RO 525 SF F310 NONE 4.50 X 80°B — SF90FT 100 B711 — —
RO 600 SF F310 NONE 2 - 2.50 X 80°B — SF90FT 100 B711 — — 30
RO 800 SF F310 NONE 2 - 3.50 X 80°B — SF90FT 100 B711 — — 30
SO 1050 SF F310 NONE 2 - 4.50 X 80°B — SF90FT 100 B711 — — 30
SO 300 SF F310 NONE 2.50 X 80°B — SF90FT 100 B711 — —
32