Boiler Guide

Basic Burner Setup Information Additional Information
Appliance
Model
Low Fire
Rate Baffle
Std. Air
Tube
Pump
Pressure
Recom.
Chassis
Approximate
Air Settings*
Insertion
Depth
Burner
Type
Head
Type
Static Plate/
Stop Screw
Nozzle
Type
Notes
Biasi / Neca / Vega / QHT (contd)
SG35D.V. AFII 150 AF2-9 # 2 0.85 X 60°B HLX70HC 140 B7210 5 5” 3
SG46 AFII 150 AF2-6 # 7 1.00 X 60°B HLX70HD 160 B7203 5 5”
SG46D.V. AFII 150 AF2-6 # 7 1.00 X 60°B HLX70HD 160 B7210 5 5” 3
B406 CF375 SL1-0 1.75 X 60°ES CF56KZ 140 BCF3907 S-9 / B-0 4-1/2”
B407 CF500 V1-2 2.25 X 60°B CF60KK 140 BCF809 S-3 / B-1 4-1/2”
B408 CF500 V1-2 2.75 X 45°P CF60KK 140 BCF809 S-7 / B-0 4-1/2”
B409 CF500 V1-4 3.00 X 30°P CF60KK 150 BCF809 S-10 / B-0 4-1/2”
B410 CF800 KH-1 3.50 X 30°P CF60KH 150 BCF403 S-7 / B-0 4-1/2”
B411 CF800 KH-2 4.00 X 45°B CF60KH 140 BCF403 S-8 / B-0 4-1/2”
B412 CF800 KHS-2 4.50 X 45°B CF60KHS 140 BCF403 S-10 / B-2 4-1/2”
B10/3 NX 6-slot 0.50 X 60°A 32229 NX70LC 180 B8001 0.75 3-1/2” 15
B10/3-DV NX 6-slot 0.50 X 60°A 32229 NX70LC 180 B8001 1.25 3-1/2” 3, 15
B10/4 NX 9-slot 0.65 X 60°B 32229 NX90LB 180 B8001 2.75 6” 40
B10/4-DV NX 9-slot 0.65 X 60°B 32229 NX90LB 180 B8001 3 6” 3, 40
B10/5 NX 9-slot 0.75 X 60°B 32229 NX90LB 180 B8001 3.75 6” 40
B10/5-DV NX 9-slot 0.75 X 60°B 32229 NX90LB 180 B8001 4 6” 3, 40
B10/6 NX 9-slot 0.90 X 60°W NX90LB 180 B8001 3.75 6” 40
B10/6-DV NX 9-slot 0.90 X 60°W NX90LB 180 B8001 4.25 6” 3, 40
SG2 NX 6-slot 0.50 X 60°A 32229 NX70LC 170 B8001 1.25 3-1/2” 15
SG2-DV NX 6-slot 0.50 X 60°A 32229 NX70LC 180 B8001 1.50 3-1/2” 3, 15
SG3 NX 9-slot 0.75 X 60°B NX90LB 180 B8001 2.50 6” 40
SG3-DV NX 9-slot 0.75 X 45°B (H) NX90LB 180 B8001 3.50 6”
3,31,40
SG4 NX 9-slot 1.00 X 60°B (H) NX90LB 170 B8001 4.50 6” 31, 40
SG4-DV NX 9-slot 1.00 X 60°B (H) NX90LB 170 B8001 4.50 6”
3,31,40
G/B7 SMG SV1-0 1.10 X 45°B (H) SMG60NR 185 B1406 S-4 / B-0 2-3/4” 31
G/B8 SMG SV1-0 1.35 X 45°B SMG82NR 185 B1406 S-4 / B-0 3”
G/B9 SMG SV1-1 1.50 X 45°B SMG82NR 185 B1406 S-4 / B-0 3”
(3) Pre/post-purge control must be used.
(9) Electrode settings of 1/4
above center of nozzle, 1/8
in front of nozzle and gap 5/32
”.
(15) Must maintain 6° downward pitch on air tube/flange.
(16) With conic shroud, “Z” dimension is 1-3/4
.
(31) The (H) in the Nozzle Description denotes a Hago.
(40) Must maintain 0° downward pitch on air tube/flange.
Bock Water Heater
120E AF F3 3-3/8” 1.00 X 80°A AF56YH 100 B3001 S-3 / B-3 5-1/8” 24
32E AF F3 3-3/8” 0.75 X 80°A AF56YH 100 B3001 S-7 / B-0 5-1/8” 24
32PP AF F3 3-3/8” 0.75 X 80°A AF56YH 100 B3001 S-7 / B-0 5-1/8” 24
33E AF F3 3-3/8” 0.75 X 80°A AF56YH 100 B3001 S-7 / B-0 5-1/8” 24
40E AF F3 3-3/8” 0.85 X 80°A AF56YH 100 B3001 S-5 / B-3 5-1/8” 24
50ES AF F3 3-3/8” 1.00 X 80°A AF56YH 100 B3001 S-3 / B-3 5-1/8” 24
51E AF F3 3-3/8” 1.00 X 80°A AF56YH 100 B3001 S-3 / B-3 5-1/8” 24
51PP AF F3 3-3/8” 1.00 X 80°A AF56YH 100 B3001 S-3 / B-3 5-1/8” 24
71E AF F6 3-3/8”R 1.25 X 80°B AF56WN 100 B3001 S-5 / B-5 5-1/8” 24
(24) Burner must be factory assembled complete with dual boiler temperature controls.
Borg-Warner
P3CFD16F08501A AFG F3H 3-3/8” 0.75 X 70°A 5880 AF47YTSS 100 B2007 S-7 / B-0 4-7/8” 27
P3CFD16F10001A AFG F3H 3-3/8” 0.90 X 70°A 5880 AF47YTSS 100 B2007 S-8 / B-0 4-7/8” 27
P3CFD16F12501A AFG F6H 2-3/4” 1.10 X 70°A 5880 AF67JPSS 100 B2007 S-8 / B-0 6-7/8” 27
P3HFB15F15001A AFG F6H 2-3/4” 1.35 X 70°A AF67JPSS 100 B2007 S-10 / B-1 6-7/8” 27
P3HFB17F12501A AFG F6H 2-3/4” 1.10 X 70°A 5880 AF67JPSS 100 B2007 S-8 / B-0 6-7/8” 27