Specifications
Start the Burner and Set Combustion
Figure 4. - Typical Wiring, R7184 Primary Control
120 VAC BURNER
START WIRE
FROM APPLIANCE
(FROM LIMIT CIRCUIT)
. L1
2°VACl :
FROM 2
APPLIANCE
EQUIPMENT
GROUND
(HOT)
(NEUTRAL)
__GROUNDSCREW
RED
BLACK
WHITE
WHITE
WHITE
WHITE
VIOLET
BLUE /
WHITE STRIPE
ORANGE
YELLOW
YELLOW
¢
¢
¢
¢
¢
¢
¢
¢
¢
¢
LIMIT
L1
L2
R7184
SERIES
PRIMARY
CONTROL
A O_----
VALVE
AO i -
IGNITION
MOTOR T 0"--"
CAD CELL T 0"--"
CAD CELL
SK9359
TO REMOTE
LOW VOLTAGE
AC ALARM
_ CIRCUIT
(IF USED)
24 VAC
THERMOSTAT
BURNER JUNCTION BOX
.... = 120 VAC FIELD WIRING
120 VAC FACTORY WIRING
- LOW VOLTAGE FIELD WIRING
- LOW VOLTAGE FACTORY WIRING
/_ = WtRENUT _ = WIRE WITH 1/4"
QUICK CONNECT
RECEPTACLE
1. STANDBY. The burner is idle, waiting for a call for
heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe
start check.
2, VALVE-ON DELAY. The ignition and motor are
turned on for a 15 second valve-on delay.
3. TRIAL FOR IGNITION (TFI). The fuel valve is
opened. A flame should be established within the
15 second lockout time.
4. LOCKOUT. If flame is not sensed by the end of
the TFI, the control shuts down on safety lockout
and must be manually reset. If the control locks out
three times in a row, the control enters restricted
lockout.
5. IGNITION CARRYOVER. Once flame is estab-
lished, the ignition remains on for 10 seconds to
ensure flame stability before turning off. If the con-
trol is wired for intermittent duty ignition, the ignition
unit stays on the entire time the motor is running.
6. RUN. The burner runs until the call for heat is sati-
fled. The burner is then sent to burner motor off
delay, if applicable, or it is shut down and sent to
standby.
Control System Features
Feature
Interrupted Limited reset, Diagnostic LED, Valve-on
ignition Limited recycle cad cell indicator delay
R7184A YES YES YES --
R7184B YES YES YES YES
R7184P YES YES YES YES
7. RECYCLE. If the flame is lost while the burner is
firing, the control shuts down the burner, enters a 60
second recycle delay, and then repeats the above
ignition sequence. If flame is lost three times in a
row, the control locks out to prevent cycling with
repetitious flame loss due to poor combustion.
8. BURNER MOTOR-OFF DELAY. The fuel valve
is closed and the burner motor is kept on for the
selected motor-off delay time before the control re-
turns the burner to standby.
P
STANOBY
RUN
Burner motor
off delay
YES
I
L_LOCKOUT I
I
i 61351
Alarm Con-
tacts
Optional
RWB 6104 BAFII R01 Page 9