Owner manual

3
GeniSys Gas Power Burner Control Installation and Operation Manual
Table 1 - Ignition Model Numbers
Model Line Model Description Part Number
Feature
120 volt Igniter
and blower motor
output
24 volt gas valve
output
2 Pin- connector
for
pressure switch
Non-volatile
lockout*
Gas Power
Burner
Standard 7590DYYYY X X X
No Pressure Switch 7590TYYYY X X
Non-volatile Manual
Reset
7590CYYYY X X X X
The standard model 7590 is designed for use on applications below 400,000 BTUs. For
applications above 400,000 BTUs, contact Beckett’s Engineering Group.
*Non-volatile lockout cannot be cleared by removing power from the control. The
control must be reset by pressing the Status/Reset button when the control is powered.
Features
For use in Natural Gas or LP gas applications.
Controls 120 Vac spark igniter, motor/blower and 24 Vac gas valve, 50/60 HZ
Provides proof of ame through ame rectication using a separate ame rod
Checks combustion air proving switch contacts (24 Vac) on 7590C and 7590D
models to prove moving combustion air and guard against welded contacts.
Field selectable for either lockout or recycle on loss of combustion air
Field selectable relight or recycle operation on loss of ame (may be factory locked)
Field selectable single or multiple trials for ignition on some models (may be locked)
Field selectable ignition timing on some models (may be factory locked)
Field selectable pre-purge timing (may be factory locked)
The microprocessor is checked for proper operation prior to each ignition cycle
Check for welded valve relays on each cycle
Mounts on standard 4 x 4 junction box
3 status LEDs supply basic diagnostics, additional diagnostic information and eld
conguration will be available through a separate diagnostic tool
An optional separate alarm module provides alarm contacts (dry contacts)
A reset button is standard on all controls, non-volatile manual reset logic is available
on specic models (7590C).
Communication Port to connect diagnostic tool and alarm module