Owner manual

17
GeniSys Gas Power Burner Control Installation and Operation Manual
Flame is not being proven, control will lockout or enter waiting period.
With power off, check the electrical connections from the control to
the ame rod.
Make sure all connections are clean and free of corrosion or build up.
Check the continuity of the ground wire and the sense wire.
The control, electrode and ame sensor must have a common ground
with the burner for proper operation.
Check the ceramic on the ame rod for any chips or cracks, replace
if needed.
Check the ame rod for build up and clean or replace if needed.
Make sure the electrode and ame rod are covered with a steady,
stable ame, adjust ame rod or electrode if needed.
Restore power, if ame is still not being proven, replace the control.
Is the yellow
Flame LED on?
Normal run mode
Note: If Flame LED is ashing slowly,
follow these same steps to improve
ame signal strength and reliability.
When the burner lights successfully, turn the thermostat or controller off to end the call for heat.
The burner should go out quickly. All LEDs on the control should go out.
If the burner remains lit for more than a few seconds, and the MV LED is out, replace the gas valve.
If the LEDs remain lit, check the thermostat or controller for proper operation.
Repeat the ignition sequence several times to make sure the system is operating properly.
YES
NO
FLAME
MV STATUS
FLAME
MV STATUS
FLAME
MV STATUS
FLAME
MV STATUS