User`s guide

Page 8 of 16 75.5652.03 20130617
14
Congure BodyGuard III
BODYGUARD III
1. Unlock BodyGuard Sensor
2. Set Output Conguration to Normally Closed
3. Lock Sensor by pressing Lock twice
NOTE: You may or may not need to adjust the BodyGuard pattern width. For instance if you are using a one door system, you must set the pattern
to ‘Center Narrow’. However if you are using a two door system, the default BodyGuard pattern will sufce. Please refer to BodyGuard User’s Guide
(75.5134) as necessary.
1
4
7
F1 F2
5
8
0
+
?
3
6
9
2
2
OUTPUT
CONFIGURATION
- Normally OPEN Relay (default)
- Normally Closed Relay
1
2
15
Check Function Number of Doors on DP-Hub
One door system:
1. Set ‘FUNCT’ Fd to ‘INCR’ 01 by rst pressing the ‘FUNCT’ button until DP-Hub display shows Fd then press ‘INCR’ button until display shows
01.
Two door system:
1. Set ‘FUNCT’ Fd to ‘INCR’ 02 (default) by rst pressing the ‘FUNCT’ button until DP-Hub display shows Fd then press ‘INCR’ button until display
shows 02.
NOTE: The above step for showing how to check and/or change a function is the same procedure for checking all functions listed in Section 6 -
Programming the DP-Hub. Please check all Programming Parameters in Section 6 before proceeding to Step 16 - Perform Door Learn. In
most applications, changing Fd will be the only necessary adjustment.
Fd = 01 Fd = 02
TWO DOORS
ONE DOOR
5 Installation (continued)
CAUTION: When using the remote control to adjust the Bodyguard, make sure you do not accidentally
change the settings on any other sensors.