User`s guide
5 Installation (continued)
8
Install Home Switch
1. Snap the Home Switch Collar with the magnetic reed switch into the correct end cap and install the end cap on the Door Mounted Sensor
extrusion. For a one door system, the correct end cap will be the cap on the leading edge of the door. For a two door system, the correct end
cap will be the leading edge or either door. The default installation will have the magnetic reed switch ush with the collar, however some
adjustment may be required. For a new install, please make sure to use the DPS Door Mounted Sensor Extrusion Mounting Template, in
order to get the extrusion with end cap installed approximately 1” apart from the surface mount adapter. For a retro t where the 1” apart can not
be obtained or for more precise Home Switch installation, please refer to
Appendix C.
2. Route the two wires from the magnetic reed switch to screw terminal on the previously installed EDPS ensuring that the wires are out of the
Door Mounted Sensor’s pattern (orientation of the two wires to the screw terminal does not matter).
For a typical one door system:
3. Press the supplied magnet into the top piece of the surface mount adapter.
4. Press the top and bottom pieces of the surface mount adapter together and install on the door jamb, using the two screws as shown above.
For a new install, please make sure to use the DPS Door Mounted Sensor Extrusion Mounting Template, in order to get the extrusion
with end cap installed approximately 1” apart from the surface mount adapter. For a retro t where the 1” apart can not be obtained or for more
precise Home Switch installation, please refer to Appendix C.
For a typical two door system:
3. Snap the supplied magnet into the second Door Mounted Sensor extrusion end cap and install the end cap on the Door Mounted Sensor
extrusion.
If you cannot use the typical installation, there are several alternatives. For more Home Switch information please refer to Appendix C.
75.5652.03 20130617 Page 5 of 16
End cap with
Home Switch
Collar exploded
Magnetic reed
switch wired
into EDPS
Surface Mount Adapter
exploded and Installed
Magnet installed in end
cap exploded and installed
9
Door Mounted Safety Side Manual Inhibit (optional)
Manually inhibiting the Door Mounted Safety Side Sensor(s) is completely optional due to the fact the DP-Hub will automatically learn the location
at which those sensor(s) go into detection during the learn cycle and then inhibit them during all consequent cycles. However if preferred to
manually inhibit those sensors using a mechanical limit switch, there are two positions available on the DP-Hub. The switch(es) must open its
contacts at the desired point of inhibiting. When these terminals are not used, they should be jumpered using the jumper included with the
package. If manually inhibiting of a Door Mounted Safety Side Sensor(s) is desired at some point in the opening cycle:
1. Cut the grey jumper wire for ‘MANUAL Stall Inhibit 1’.
2. Wire the mechanical inhibit switch to the previously cut jumper wires and wire nut.
For a two door system, repeat steps above using the orange jumper wire.
NOTE: See Programming Parameter
FM on page 10 section 6-1.
Door Mounted 1
Manual Inhibit
Door Mounted 2
Manual Inhibit
Door Mounted Sensor needs
inhibited automatically by
DP-Hub or manually
Door Mounted Sensor Manual
Inhibit Jumper