Instruction manual

PROCEDURE 4REFRIGERANT TUBING
Use accessory tubing package or field-supplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or
contaminated tubing because it may plug refrigerant flow-control device. ALWAYS evacuate the coil and field-supplied tubing to 500 microns
before opening outdoor unit service valves.
CAUTION: Braze with Sil-Fos or Phos-copper on copper to copper joints and wrap a wet cloth around rear of fitting
to prevent damage to TXV.
PROCEDURE 5REFRIGERANT FLOW-CONTROL DEVICE
CAUTION: If using a TXV (FC4B factory installed) in conjunction with a single-phase reciprocating compressor, a
compressor start capacitor and relay are required. Consult outdoor unit pre-sale literature for start assist kit part no.
Replace piston if required. Check piston size shown on indoor unit rating plate to see if it matches required piston shown on outdoor unit rating
plate. If it does not match, replace indoor piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any
approved indoor coil combination. (See Fig. 16.) When changing piston, use a back-up wrench. Hand tighten hex nut, then tighten with wrench
1/2 turn. Do not exceed 30 ft-lbs.
Fig. 11Wiring Layout Heat Pump Unit
(Cooling and 2-Stage Heat with No Outdoor Thermostat)
A94060
R
G
C
E
L
O
Y
THERMOSTAT
R
R
C
O
Y
G
C
W
2
W
2
W
2
W
3
E
FAN COIL
(CONTROL)
HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
Fig. 12Wiring Layout Heat Pump Unit
(Cooling and 2-Stage Heat with 1 Outdoor Thermostat)
A94061
R
G
C
E
L
O
Y
THERMOSTAT
R
R
C
O
Y
G
C
W
2
W
2
W
2
W
3
E
ODTS
FAN COIL
(CONTROL)
HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
VIO
BLU
9