Install traps in the condensate lines as close to the coil as possible. (See Fig. 19.) Make sure that the outlet of each trap is below it connection to
the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living
area.
Condensate drain lines should be pitched downward at a minimum slop of 1 in. for every 10 ft of length.
Consult local codes for additional restrictions or precautions.
Fig. 17Recommended Condensate Trap
A02006
2″ ΜΙΝ
2″ ΜΙΝ
UNIT
Fig. 18Insufficient Condensate Trap
A95320
DO NOT USE SHALLOW RUNNING TRAPS!
Fig. 19Condensate Drain
A02004
FILTER
ACCESS
PANEL
SECONDARY DRAIN REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)
PRIMARY TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF
SUFFICIENT DEPTH.
STANDARD PRIMARY TRAPS
ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENEDED
CONDENSATE TRAP)