7.5. Structure of the menu system
7.6 Menu list
8. Placing out of service
WARNING! Disassemble the device only in current and
pressure less condition!
9. Maintenance
DANGER! The operator is obligated to observe the
information concerning operation and maintenance work
on the warning signs possibly affixed to the device.
In principle, this device is maintenance-free. If desired, the
housing of the device can be cleaned using a damp cloth
and non-aggressive cleaning solutions, in switched-off state.
10. Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it has to be cleaned
carefully and packed shatter-proofed. You have to enclose a
notice of return with detailed defect description when sending
the device. If your device came in contact with harmful
substances, a declaration of decontamination is additionally
required. Appropriate forms can be downloaded from our
homepage www.bdsensors.de. Should you dispatch a
device without a declaration of decontamination and if there
are any doubts in our service department regarding the used
medium, repair will not be started until an acceptable
declaration is sent.
If the device came in contact with hazardous
substances, certain precautions have to be
complied with for purification!
11. Disposal
The device must be disposed of according to the
European Directive 2012/19/EU (waste electrical
and electronic equipment). Waste equipment
must not be disposed of in household waste!
Dispose of the device properly!
12. Warranty terms
The warranty terms are subject to the legal warranty period
of 24 months, valid from the date of delivery. If the device is
used improperly, modified, or damaged, we will rule out any
warranty claim. A damaged diaphragm will not be accepted
as a warranty case. Likewise, there shall be no entitlement to
services or parts provided under warranty if the defects have
arisen due to normal wear and tear.
menu 1 – access protection
PAon
password active
to deactivate: set password
PAof
password inactive
to activate: set password
default setting for the password is "0005"; modification of the password is described in special menu 4
menu 2 – set decimal point position
For devices with LC display – in case no decimal point shall be displayed – the colon between digit 3 +4 is
displayed in the selection menu "dP".
menus 3 and 4 – set zero point / end point
the device has been configured correctly before delivery, so a later setting of a 2-wire device is only
necessary, if a differing displayed value is desired (e. g. 0 ... 100 %)
menu 5 – set damping
this function allows getting a constant display value although the measuring values may vary considerably; the time
constant for a simulated low-pass filter can be set (0.3 up to 30 sec permissible)
menu 6 – exceeding message
set "on" or "off"
menus 7 and 9 – set switch-on points
set the particular values, for the activation of contact 1 (S1on) up to 2 (S2on)
menus 8 and 10 – set switch-off points
set the particular values, for the deactivation of contact 1 (S1oF) up to 2 (S2oF)
menus 11 and 12 – select hysteresis or compare mode
select the hysteresis mode (HY 1 up to HY 2) or compare mode (CP 1 up to CP 2) for the contacts 1 up to 2
(no. corresponds to the contact)
compare "7.4. Description of hysteresis and compare mode"
menus 13 and 15 – set switch-on delay
set the particular value of the switch-on delay after reaching contact 1 (d1on) up to 2 (d2on)
(0 up to 100 sec permissible)
menus 14 and 16 – set switch-of delay
set the particular value of the delay after reaching the switch-off point 1 (d1of) up to 2 (d2of)
(0 up to 100 sec permissible)
menus 17 and 18 – maximum / minimum pressure display
view high pressure (HIPr) or low pressure (LoPr) during the measurement process
(the value will not remain stored if the power supply is interrupted)
to erase: push both buttons again within one second
special menus
(to access a special menu, select the menu item "PAof" with the ▲- or ▼-button and confirm it; "1" appears in the display)
special menu 1 – full scale compensation
for full scale compensation, which is necessary if the indicated value for full scale differs from the real full scale
value in the application (a compensation is only possible with a respective reference source, if the deviation of the
measured value is within defined limits); set "0238"; confirm with both buttons; "FS S" will appear in the display;
now it is necessary to place the device under pressure (the pressure must correspond to the end point of the
pressure measuring range); push both buttons, to store the signal being emitted from the device as full scale; in
the display the set end point will appear although the full scale sensor signal is displaced
the analogue output signal (for devices with analogue output) is not affected by this change
special menu 2 – offset compensation / position correction
set "0247";
special menu 3 – load defaults
set "0729
special menu 4 – set password
set "0835"; confirm with both buttons; "SEtP" appears in the display; set the password using the ▲- or ▼-button
(0 ... 9999 are permissible, the code numbers 0238, 0247, 0729, 0835 are exempt); confirm the password by
pushing both buttons simultaneously
- ▲-button: move in the menu system (forward) or increase the displayed value
- ▼-button: move in the menu system (backward) or decrease the displayed value
- both buttons simultaneously: confirm the menu items and set values or change between display
and configuration mode
to increase the counting speed, when setting the values: keeping the respective button pushed for more than
5 seconds
Execution of configuration:
- set the desired menu item by pushing the ▲- or ▼-button
- activate the set menu item by pushing both buttons simultaneously
- set the desired value or select one of the offered settings by using the ▲- or ▼-button
- store the set value / selected setting and exit the menu by pushing both buttons simultaneously
13. Declaration of conformity / CE
The delivered device fulfils all legal requirements. The applied directives, harmonised standards and documents are listed
in the EC declaration of conformity, which is available online at: http://www.bdsensors.de. Additionally, the operational safety is
confirmed by the CE sign on the manufacturing label.