Owner`s manual

RPC SERIES OWNER’S MANUAL
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
53
Outlet Power-Up Delay The Outlet Power-up delay allows a set
amount of time to elapse after a unit power-
up or user initiated reset before power is
applied to the outlet. This power up
sequence is also used when a REBOOT
occurs.
From the Outlet Configuration Menu, select
#3 (or #4), “Outlet Power-up Delay.” The
unit responds:
To set delay, enter number of outlet, CR to exit
Outlet power-up delays (in seconds):
1) . . . Outlet 1 : 0
2) . . . Outlet 2 : 0
3) . . . Outlet 3 : 0
4) . . . Outlet 4 : 0
5) . . . Outlet 5 : 0
6) . . . Outlet 6 : 0
7) . . . Outlet 7 : 0
8) . . . Outlet 8 : 0
Enter Request >
Enter the number of the outlet to set a
power-up delay, followed by <cr>. The unit
responds:
Outlet Name: Outlet 1
Enter delay (seconds) >
Enter the amount of time (up to 599
seconds) to elapse before power is applied to
the outlet. The RPC Series redisplays the
power-up delay status reflecting the change.
Name Outlets “Name Outlets” allows the user to customize
outlet name(s) to identify individual pieces
of equipment attached to the RPC. From the
RPC’s configuration menu, the user can
change any or all outlet names to outline a