Owner`s manual

RPC SERIES OWNER’S MANUAL
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
32
RPC-2 Series
(c) 1997 by BayTech
F2.07
Circuit Breaker : On
1) . . . OUTLET 1 : Off
2) . . . OUTLET 2 : Off
3) . . . OUTLET 3 : On
4) . . . OUTLET 4 : Off
5) . . . OUTLET 5 : Off
6) . . . OUTLET 6 : Off
RPC >
Likewise, typing ON 0 at the RPC > prompt
and responding “Y” for yes, turns “On” all
outlets. Typing OFF n at the RPC > prompt
turns off corresponding outlet(s).
The REBOOT n command will reboot or
reset equipment attached to corresponding
receptacle(s). When the command to
REBOOT (n) is sent from the RPC >
prompt, the RPC powers “Off”
corresponding outlet(s) for approximately 10
seconds, then powers them up in sequence.
This command only works on outlets which
were “On” prior to the reboot.
Accessing Main Menu Using communications software, dial the
via Modem modem using the ATDT command. If the
modem does not respond in 5 to 7 rings, the
RPC’s RDR feature recycles power to Outlet
6 and consequently resets the modem. Dial
the modem again using the ATDT
command. When a connection has been
established, the RPC sends the following
header:
RPC-2 Series
(C) 1997 by BayTech
F2.07