Owner`s manual

RPC SERIES OWNER’S MANUAL
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
31
Accessing Main Menu Power on the RPC unit. The following
outlet and circuit breaker status menu
appears:
RPC-2 Series
(c) 1997 by BayTech
F2.07
Circuit Breaker : On
1) . . . OUTLET 1 : Off
2) . . . OUTLET 2 : Off
3) . . . OUTLET 3 : Off
4) . . . OUTLET 4 : Off
5) . . . OUTLET 5 : Off
6) . . . OUTLET 6 : Off
RPC >
If the status menu fails to appear, ensure the
correct cables and adapters are being used
and that they are connected properly. Also,
verify the serial communication parameters
are correctly configured.
Controlling Receptacles To set or change the status of receptacles,
enter one of the following commands: ON
n, OFF n, REBOOT n, where “n” is the
outlet number you want to command.
Entering an outlet number of “0” sends the
command to all outlets.
Example: To turn “On” Outlet 3, type ON 3 from the
RPC prompt (RPC >). The RPC responds:
Turn On Outlet 3 (Y/N)?
Responding “Y” for yes turns “On” Outlet 3.
Observe that the status of Outlet 3 has
changed to On in the status menu: