Owner`s manual

RPC SERIES OWNER’S MANUAL
RPC SERIES QUICK START (RPC3-15/20, RPC-3A, RPC-5, RPC-7 AND RPC-21)
________________________________________________________________________________
9
RPC3-15/20, RPC-3A, RPC-5, RPC-7 AND RPC-21
QUICK START
NOTE: The RPC3-15/20, 3A, 5, and 7 are configured in a similar
manner. This quick start will reference the RPC-3 menus.
Programming differences for the RPC-5 and 7 pertain to the
number of receptacles shown in the menus (4 or 12 vice 8). The
current monitoring function is discussed separately on page 59.
NOTE: Inlet #1 supplies power to the logic of the RPC-5, this
inlet must have power for the unit to operate.
Local access Using the 9FRJ45PC-1 adapter and the
using EIA-232 serial RJ08X007 (8-pin crossed) cable, connect the
connection serial port of your computer to the RJ-45
port labeled “EIA-232” on the RPC unit.
Remote access using Using a straight 10Base-T cable, connect
network port the port labeled Ethernet on the RPC to the
connection network hub. Establish a Telnet client
session and login from your workstation.
Load serial port communications software. Set
serial communications parameters to 9600
bps, 8 data bits, 1 stop bit, and no parity.
OPERATION
Accessing Main Menu Power on the RPC unit. The following main
menu appears: