Owner`s manual
M SERIES DAC
BASE UNIT AND MODULE CONFIGURATION
____________________________________________________________________________
45
for the base unit. No characters should be typed between
$BT0<cr> and $CONFIG<cr>.
To access the configuration mode of the base unit from the service port or service
modem, use the following procedure:
SERVICE PORT OR SERVICE MODEM ACCESS
1. If configuring from the service port, connect a terminal to the EIA-
232 service port and configure the terminal's serial parameters to
9600 baud rate, 8 word size, 1 stop bit, and no parity. If
configuring from the service modem, establish a connection
between the remote terminal and service modem by dialing into the
service modem. Once the unit is powered on, the following
message will be sent out of the service port:
Bay Technical Associates
Service Port
Firmware Revision 4.XX
This same message will be sent to the remote modem once a
connection is established with the service modem. The service
modem has priority over the EIA-232 service port. When a
connection is established between a remote modem and the service
modem, the following message will be sent out of the EIA-232
service port:
Incoming call
Service port access locked out
A terminal connected to the EIA-232 service port is not allowed
access to the M Series unit while the service modem has a
connection with a remote modem. If a user connected to the EIA-
232 service port is currently communicating with the M Series unit
and a remote user attempts to access configuration mode through
the service modem, the remote user is not allowed access to the M
Series unit.
2. Place the base unit or desired module into command mode by
sending $BT0n<cr>. (Use $BAYTECHn<cr> with M4 and M8
DAC units).