set of normally open (NO) and normally closed (NC) contacts and is capable of
switching AC and DC loads up to 3 amps. The V78 CRM-1 employs
electromechanical relays having zero current leakage and can be used to switch very
low-current loads. All relays may change state on demand via data commands or
time schedule.
Individual relay status may be presented to a host system automatically or upon
request. The relay status may be the current state or change-in-state history of a
specific relay. Data associated with the relay status which is generated by the V78
CRM-1 and sent to the host system will be referred to as a data message. Data
messages consist of the actual relay status (energized or de-energized) preceded by
the appropriate unit/module/relay number and may include a Time Tag showing the
date and time the relay status was recorded. Data messages are supplied to the host
system upon request, at a specific time, or as events occur. An event is the change-in-
state of a relay.
You have the choice of programming the V78 CRM-1 via verbose (menu-driven) or
non-verbose (dynamic) configuration mode. When using verbose configuration
mode, a series of menus will prompt you to enter the desired configuration
parameters. Non-verbose or dynamic configuration mode allows you to program
certain parameters of the V78 CRM-1 by downloading configuration. You may
review the current V78 CRM-1 configuration status from the control panel.
USER-PROGRAMMABLE FEATURES
You may program the Relay Operating Setup, Reporting Setup, and Dynamic
Configuration on the V78 CRM-1.
RELAY OPERATING SETUP
Relay Operating Setup allows you to program the V78 CRM-1 relay time schedule.
You may view the current relay schedule, create and/or modify the current schedule,
enable or disable individual events, and delete individual events. The default relay
schedule is null (no schedule).
REPORTING SETUP
Reporting Setup allows you to program how the V78 CRM-1 reports data messages
to the host module. The items you may program in the Reporting Setup include
Reporting Method, Report Start Time, Report Interval, Set Host Address, Time Tag,
and Terminating Character(s).
REPORTING METHOD