Owner`s manual

M SERIES DAC
BASE UNIT AND MODULE OPERATION
____________________________________________________________________________
112
8) “Rtel”----Reverse Telnet Operation. When users want to prevent
V71, V93A, or service port users from gaining access to the network
through the V72/V72TP, the reverse Telnet feature may be disabled.
The default setting for “Rtel” (Reverse Telnet Operation) Is enabled.
V72 HOST CONNECTION
The V72 host module requires a physical network connection to perform data
acquisition and control functions with the M-Series modules. The V72 supports
10BASE2 or 10BASE-T Ethernet connections with Ethernet II or 802.3 SNAP framing.
IP version 4 is required and TCP connections may be established to the TELNET via A
TELNET client or any ephemeral port (port number above 1024). The latter form of
connection requires the user to develop workstation code, but allows for automated unit
access and disposition of data. Use the following procedure to access the M-Series
modules through the V72 host module:
1. Open a session to the V72 module using any workstation TELNET
client or ephemeral You will be presented with a welcome screen (if
enabled) and a login prompt (if enabled) upon successful
establishment of the session similar to the following:
M-Series V72 DAC Host
Unit: 1 Module: 1
F 0.28, copyright (c) 1995-1997
Bay Technical Associates
To login, enter password.
Login:
NOTE: You will not get the welcome message and/or the login prompt if
either one of these options are disabled in configuration mode.
2. Enter the password at the login prompt (if enabled).
3. If the login procedure is enabled, you will receive a "Login
Successful" message and a prompt to enter a selection if the
password is successfully entered. At this point, you may configure
modules, connect to ports, receive messages, etc.. The V72 can route
data from a peripheral communications module operating in
Immediate Message mode or Immediate Data mode to one and only
one network workstation. A network workstation must send a
command to the V72 module to receive messages or data. This
command consists of the port select code ($BT - default), capital "I",