Owner`s manual

M SERIES DAC
BASE UNIT AND MODULE CONFIGURATION
____________________________________________________________________________
89
the following procedure to send dynamic configuration commands to the V78 CRM-
1:
1. Select the V78 CRM-1 from a config port by sending a select
sequence which consists of the port select code ($BT - default), the
appropriate unit number followed by a colon (01: to 30: - for
cascaded units only), the desired module number (2 to 16), and a
terminating character for <cr> (0D Hex). For example, to select a
V78 CRM-1 Module installed as Module 15 of a non-cascaded unit
using the default port select code, send $BT15<cr>.
2. Once the V78 CRM-1 is selected, it enters Command Mode and
allows you to send dynamic configuration commands. The V78
CRM-1 configuration commands begin with two capital letters
designating the specific command and are terminated with <cr>.
Most configuration commands require a number between the
command letters and <cr>. This number represents the desired
configuration parameter.
3. After you have sent the desired configuration command(s) to the
V78 CRM-1 module, you may disconnect by sending $BT<cr>.
You may disconnect from the V78 CRM-1 and select a different
module or the base unit by sending $BTn<cr>.
NOTE: Multiple configuration commands may be sent while the V78
CRM-1 is in command mode. Each command should be terminated with
<cr>. For example:
RM1<cr>TT2<cr>
REPORTING METHOD COMMAND
The Reporting Method (RM) command programs the V78 CRM-1 Reporting Method.
The Reporting Method command has the following format:
RMn<cr>
where n = 1 to 3 (1 = Command, 2 = Immediate and 3 = Schedule).
TIME TAG COMMAND
The Time Tag (TT) command is used to enable or disable time. The Time Tag
command has the following format: