Owner`s manual

58
If the enable/disable feature is disabled, the RPC will not
ask to confirm the command.
From the Outlet Operation Configuration Menu, select #2,
“Command Confirmation.” Depending on whether
confirmation is currently enabled or disabled, the
RPC responds with the option to change the current status.
NOTE The factory default setting is Enabled:
Disable Confirmation? (Y/N)
Outlet Power-up Delay
The Outlet Power-up delay allows a set amount of time to
elapse after a unit power-up or user initiated reset before
power is applied to the outlet. This power up sequence is
also used when a REBOOT occurs.
RPC OWNER’S MANUAL
____________________________________________________________
From the Outlet Configuration Menu, select #3, “Outlet
Power-up Delay.” The unit responds:
To set delay, enter number of outlet, CR to exit
Outlet power-up delays (in seconds):
1) . . . Outlet 1 : 0
2) . . . Outlet 2 : 0
3) . . . Outlet 3 : 0
4) . . . Outlet 4 : 0
5) . . . Outlet 5 : 0
6) . . . Outlet 6 : 0
7) . . . Outlet 7 : 0
8) . . . Outlet 8 : 0
Enter Request >
Enter the number of the outlet to set a power-up delay,
followed by a carriage return <cr>. The unit responds:
Outlet Name: Outlet 1
Enter delay (seconds) >