Owner`s manual

30
The factory default outlet names are Outlet 1, Outlet 2, Outlet 3 . . . Outlet
6. From the RPC’s configuration menu, the user can change any outlet
name to outline a unique set-up.
RPC-2
From the status menu’s RPC > prompt, type CONFIG. The following
menu appears:
RPC > CONFIG
1) . . . Change Password
2) . . . Change Outlet Name
Enter Request:
RPC-2A
From the status menu’s RPC > prompt, type CONFIG. The following
menu appears:
1) . . . Change Password
2) . . . Change Outlet Name
3) . . . Enable/Disable Confirmation
4) . . . RPC > CONFIG
5) . . . Enable/Disable Status Menu
X) . . . Exit
Enter Request:
1. Change Password
RPC-2/RPC-2A
Select #1, “Change Password,” and press <Enter.> The RPC responds:
Enter Current Password:
Since the factory default password is a carriage return, hit <Enter.> If this
is not an initial set-up and a password has already been set, enter the
current password, followed by a carriage return. If you enter the password
incorrectly, the RPC responds with an “Error” message and returns to the
main menu. Consequently, you must start over by typing “CONFIG” to
access the configuration menu. If you enter the current password
correctly, the RPC responds:
Enter New Password:
RPC-2/RPC-2A OPERATIONS & CONFIGURATION