RPC OWNER’S MANUAL ____________________________________________________________ 1.0 INTRODUCTION TO THE REMOTE POWER CONTROL SWITCH (RPC) The BayTech RPC-Series is a full-featured AC power management solution that provides an easy way to control power of remote equipment. From your office or from anywhere, the RPC will TURN ON, TURN OFF, OR REBOOT remote equipment. There are six different RPC models. Four models operate at 115 VAC, 15 Amp. Two models operate at 230 VAC, 10 Amp.
RPC OWNER’S MANUAL ____________________________________________________________ This document provides information required for installing and operating your Remote Power Control Unit. It should allow the user to connect, power up, and access an applications menu where the power of connected equipment can be controlled. We suggest reading this manual carefully, while placing special emphasis on correct cabling and configuration.
RPC-2 AND RPC-2A QUICK START ____________________________________________________________ 2.1 RPC-2 AND RPC-2A QUICK START EIA-232 SERIAL CONNECTION RPC-2/RPC-2A Using the 9FRJ45PC-1 adapter and the RJ08X007 cable, connect the serial port of your computer to the RJ-45 port labeled “EIA-232.” Load serial port communications software. Set serial communications parameters to 9600 bps, 8 data bits, 1 stop bit, and no parity. OPERATION Accessing Main Menu RPC-2/RPC-2A Power on the RPC unit.
RPC OWNER’S MANUAL ____________________________________________________________ Also, verify the serial communication parameters are correctly configured. Controlling Receptacles RPC-2/RPC-2A CONFIGURATION RPC-2 To set or change the status of the receptacles, enter one of the following commands: ON n, OFF n, REBOOT n, where “n” is the outlet number you wish to send the command. Entering an outlet number of “0” sends the command to all outlets. Type “CONFIG” from the RPC>prompt.
RPC-2/RPC-2A QUICK START ____________________________________________________________ disabled from the factory. The factory default password is a carriage return. The RPC prompts for the old password. Enter a carriage return. The RPC prompts for a new password. Enter a new password (maximum field length, 8 alphanumeric characters). NOTE: The password feature is case sensitive. The RPC asks you to confirm the new password. A message confirms success of the password change.
RPC OWNER’S MANUAL ____________________________________________________________ Enable/Disable Status Menu RPC-2A From the configuration menu, select #4, “Enable/Disable Status Menu.” The RPC responds with the option to toggle the status menu on or off.. NOTE The factory default setting is Enabled: Disable Status Menu? (Y/N) 2.
RPC-2 MD01/RPC-2 RDR QUICK START ____________________________________________________________ RPC-2 Series (c) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . . OUTLET 6 : : : : : : Off Off Off Off Off Off RPC > If the status menu fails to appear, ensure the correct cables and adapters are being used and that they are connected properly. Also, verify the serial communication parameters are correctly configured.
RPC OWNER’S MANUAL ____________________________________________________________ Change Password Select #1, “Change Password,” press NOTE The factory default password is disabled by making the password a carriage return. The RPC prompts for the old password. Enter a carriage return. The RPC prompts for a new password. Enter a new password (maximum field length, 8 characters). The RPC asks you to confirm the new password. A message confirms success of the password change.
RPC-2 MD01/RPC-2 RDR QUICK START Using the RJ04X007 (RJ-11) modular cable, connect either port labeled “LINE” on the RPC unit to the telco wall jack. Using another RJ04X007 (RJ-11) modular cable, connect the remaining port labeled “LINE” on the RPC unit to the port labeled “LINE” on the external modem. Using the 25MRJ45MD-8 adapter and the RJ08X007 (8-pin crossed) cable, connect the DB-25 female port of the modem to the RJ-45 port labeled “EIA-232” on the back of the RPC unit.
RPC OWNER’S MANUAL ____________________________________________________________ RPC-2 Series (C) 1997 by BayTech F2.07 Enter Password If prompted, enter password. The following main menu appears. RPC-2 Series (C) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . .
RPC-3 AND RPC-3A QUICK START ____________________________________________________________ 2.3 A QUICK START FOR RPC-3, RPC-3A and RPC-5 RPC-5 Note: The RPC-3 and RPC-5 are configured in a similar manner. This quick start will reference the RPC-3 menus. The only programming differences for the RPC-5 pertain to the number of receptacles shown in the menus. NOTE: Inlet #1 supplies power to the logic of the RPC-5, this inlet must have power for the unit to operate.
OPERATION Accessing Main Menu Power on the RPC unit. Hit The following main menu appears: RPC-3 Telnet Host Revision F 3.03, (C) 1998 Bay Technical Associates Unit ID: RPC3 RPC-3 Menu: 1) . . . Outlet Control 2) . . . Manage Users 3) . . . Configuration 4) . . . Unit Status 5) . . . Reset Unit 6) . . .
PC OWNER’S MANUAL If the main menu fails to appear, ensure the correct cables and adapters are being used and that they are connected properly. Also, verify the serial communication parame ters are correctly configured. Outlet Control To set or change the status of the receptacles, select #1 “Outlet Control” from the main menu. From the RPC> prompt, enter one of the following commands: ON n, OFF n, REBOOT where “n” is the outlet number you wish to send the command.
1) . . . Add user 2) . . . admin The “Add user” option is presented any time less than 8 users are defined. The “Delete RPC-3 AND RPC-3A QUICK START ____________________________________________________________ user” option is presented any time one or more optional outlet users are defined. Deletion of admin user is prohibited. Change Password From the User Management Menu, select the number of the user to modify, followed by a carriage return .
CONFIGURATION IMPORTANT: For network access, you must configure the IP address, subnet mask, and gateway from the serial port. RPC OWNER’S MANUAL ____________________________________________________________ NOTE: Network parameters, such as IP Address, require a unit reset. All other changes take affect immediately upon accepting changes after exiting configuration. Select #3, “Configuration” from the main menu. The following menu appears: Bay Technical Associates RPC-3 Configuration Menu MAC Addr: 00.
Gateway Select #3, “ Gateway.” Enter the RPC unit’s Gateway address in dotted decimal format (200.4.5.50). Unit ID Select #4, “Unit ID.” Enter the RPC unit’s Unit ID (64 chars max). RPC-3 AND RPC-3A QUICK START ______________________________________________________ Access NOTE If username and password are disabled (factory default), outlet users will have access to all admin functions. From the configuration menu, select #5, “Access,” followed by a carriage return .
5) Display Outlet Users – A display of outlet user assignments. RPC OWNER’S MANUAL ____________________________________________________________ UNIT STATUS From the main menu, select #4, “Unit Status,” followed by a carriage return. The RPC sends a Unit Status Menu that provides vital information about the RPC—system status, network interface, logged user status, and outlet status. Select the number of the status to review.
RPC INSTALLATION ____________________________________________________________ 3.0 INSTALLATION 3.1 UNPACKING Compare the unit and serial number of the equipment you received to the packing slip located on the outside of the box. Inspect equipment carefully for damage that may have occurred in shipment. If there is damage to the equipment or if materials are missing, contact BayTech technical support at 228-467-8231 or call toll free inside the United States at 800-523-2702.
The installation area should be clean and free of extreme temperatures and humidity. Allow sufficient space behind the RPC unit for cabling and receptacle connections. 3.3 SAFETY OPERATIONS When operating, installing, maintaining, transporting, or storing equipment, take the following special precautions to avoid the introduction of hazards. RPC OWNER’S MANUAL ____________________________________________________________ CAUTION For indoor use only.
9. Do not attempt to modify any portion/component of an RPC unit. BayTech or another authorized service technician must perform any internal changes. For more information, please contact BayTech at 228-467-8231 or call toll free inside the United States at 800-523-2702. Applying power illuminates a green LED on the front panel of the RPC. When the power switch is off , devices connected to the unit are not receiving power (off).
through the circuit breaker. If an overload condition occurs, the RPC status menu is still accessible. If all circuits are closed, the circuit breaker status menu will indicate “On.” If the circuit breaker is tripped, the circuit breaker status will indicate “Off.” RPC OWNER’S MANUAL ____________________________________________________________ 3.7 GROUND High-voltage surges and spikes can damage this equipment.
Fig. 1: RJ-45 Receptacle Fig. 2: RJ-45 Plug CABLING The RPC RJ-45 control port uses the following signals: EIA-232 RJ-45 CONTROL PORT PIN/SIGNAL DEFINITION 22 Pin EIA-232 Signal Direction Description 1 DTR Output +10V when activated by DCD. Toggles on logout for modem disconnect.
RJ-45 1 BLUE 2 ORANGE 3 BLACK 4 RED 5 GREEN 6 YELLOW 7 BROWN 8 GRAY 2 TX 3 RX 4 RTS 5 CTS 6 DSR 7 GND 8 DCD FEMALE DB-25 20 Figure 3: Computer/Terminal Adapter BayTech Part No. 25FRJ45PC-1 DTR Crossed RJ-45 cable is required RPC OWNER’S MANUAL ____________________________________________________________ To interface a computer or terminal to the RPC, refer to comment on Page 20. Refer to Figure 3, if the host computer or terminal has a DB-25 male connector.
RJ-45 1 BLUE 2 ORANGE 3 BLACK 4 RED 5 6 1 DCD 2 RX 3 TX 4 DTR 5 GND 6 DSR 7 RTS 8 CTS FEMALE DE-9 GREEN YELLOW 7 BROWN 8 GRAY Figure 4: Computer/Terminal Adapter BayTech Part No. 9FRJ45PC-1 Crossed RJ-45 cable is required Modem Communications: A modem can be connected to the EIA-232 serial port by using a 25MRJ45MD-8 adapter (Figure 5). Modem adapters are available from BayTech. Contact BayTech Technical Support for purchase information.
To interface an asynchronous modem to the RPC refer to Figure 5. 1 2 3 4 RJ45 5 6 7 8 2 3 4 DB25 5 MALE 6 7 8 20 Figure 5: Modem Adapter BayTech Part No. 25MRJ45MD-8 Crossed RJ-45 cable is required RJ-45 RJ-45 CONDUCTOR PIN PIN 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 COLOR COLOR BLUE ORANGE BLUE BLACK BLACK RED RED GREEN GREEN YELLOW BROWN ORANGE YELLOW GRAY BROWN GRAY Figure 6: Crossed 8-pin Modular Cable BayTech Part No.
IMPORTANT: Crossed RJ-45 cables are required when modular connectors are used, as shown in Figures 3 – 5, or to interface the RPC to another BayTech product with modular connectors, such as the DS-Series data switch. See the cable diagram on Page 23. 5.0 OPERATION AND CONFIGURATION The following section, “Operation and Configuration,” provides a detailed approach to accessing, operating, and configuring the RPC. NOTE It is important that you type all commands correctly.
If your computer does have a RJ-45 connection, but the pin signals are different from those described for BayTech on Page 20 of this manual, it is possible for BayTech to customize an adapter for you. If you require a different adapter than the one supplied with this unit, contact BayTech’s Applications Engineers.
Accessing Main Menu Power on the RPC unit. The following status menu appears: RPC-2 Series (c) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . . OUTLET 6 : : : : : : Off Off Off Off Off Off RPC > If the status menu fails to appear, ensure the correct cables and adapters are being used and they are connected properly. Also, verify the serial communication parameters are correctly configured.
RPC-2 Series (c) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . . OUTLET 6 : : : : : : Off Off On Off Off Off RPC > Likewise, typing ON 0 at the RPC > prompt and responding “Y” for yes, turns “On” all outlets. Typing OFF n at the RPC > prompt turns off corresponding outlet(s). The REBOOT n command will reboot or reset equipment attached to corresponding receptacle(s).
The factory default outlet names are Outlet 1, Outlet 2, Outlet 3 . . . Outlet 6. From the RPC’s configuration menu, the user can change any outlet name to outline a unique set-up. RPC-2 From the status menu’s RPC > prompt, type CONFIG. The following menu appears: RPC > CONFIG 1) . . . Change Password 2) . . . Change Outlet Name Enter Request: RPC-2A From the status menu’s RPC > prompt, type CONFIG. The following menu appears: 1) . . . Change Password 2) . . . Change Outlet Name 3) . . .
Enter a new password (maximum field length, 8 alphanumeric characters), followed by a carriage return. The RPC responds: Re-Enter New Password: Re-enter the new password identically to the first entry. Remember that the password feature is case sensitive. If you fail to re-enter the new password correctly, the RPC responds with an “Error” message and returns to the main menu. Consequently, must start over by typing CONFIG” from the RPC > prompt to access the configuration menu.
Enter the number of the outlet you want to change. If you want to change the name of Outlet 4, type the number 4 at the “Enter Request” prompt, followed by a carriage return. The RPC responds: Enter: Enter a new receptacle name (maximum field length, 10 characters), followed by a carriage return. If you want to change the name of Receptacle 4 from Outlet 4 to Router 1, type Router 1 from the “Enter” prompt, followed by a carriage return.
From the configuration menu, select #3, “Enable/Disable Confirmation.” Depending on whether confirmation is currently enabled or disabled, the RPC responds with the option to change the current status. NOTE The factory default setting is Enabled: Disable Confirmation? (Y/N) 4. Enable/Disable Status Menu RPC-2A From the configuration menu, select #4, “Enable/Disable Status Menu.” If the Enable/Disable Status Menu feature is enabled, the following status menu appears.
5.2 RPC-2 MD01 AND RPC-2 RDR 5.2.1 LOCAL ACCESS 5.2.1.1 EIA-232 SERIAL CONNECTION The RPC-2 MD01 and RPC-2 RDR have an RJ-45 port for connecting to a local EIA-232 device, such as a computer terminal or external modem. Most serial computers do not have RJ-45 connections; therefore, an adapter is provided with this unit to convert from a DE-9 connector to an RJ-45 connector (BayTech Part No. 9FRJ45PC-1). If you are connecting to a modem, use a modem adapter (BayTech Part No. 25MRJ45MD-8).
5.2.1.3 LOCAL OPERATION The RPC’s main menu allows you to monitor and control equipment attached to each of the RPC-2 RDR and RPC-2 MD01’s six receptacles. From this menu, you can turn on, turn off, or reboot attached equipment, individually, or all equipment, simultaneously. The RPC recognizes three basic operating commands: ON n, OFF n, and REBOOT n, where n represents the outlet number and represents a carriage return. There are six red LEDs on the front of the RPC unit.
If the status menu fails to appear, ensure the correct cables and adapters are being used and that they are connected properly. Also, verify the serial communication parameters are correctly configured. Controlling Receptacles To set or change the status of receptacles, enter one of the following commands: ON n, OFF n, REBOOT n, where “n” is the outlet number you wish to send the command. Entering an outlet number of “0” sends the command to all outlets.
The REBOOT n command will reboot or reset equipment attached to corresponding receptacle(s). When the command to REBOOT (n) is sent from the RPC > prompt, the RPC powers “Off” corresponding outlet(s) for approximately 10 seconds, then returns them to the state they were (“On” or “Off”) prior to receiving the reboot command. 5.2.1.
Since the factory default password is a carriage return, hit If this is not an initial set-up and a password has already been set, enter the current password, followed by a carriage return. If you enter the password incorrectly, the RPC responds with an “Error” message and returns to the main menu. Consequently, you must start over by typing “CONFIG” to access the configuration menu.
“Re-enter New Password” prompt. Changing the new password to a carriage return disables password protection. See Programming a Password above. 2. Change Outlet Name From the status menu’s RPC > prompt, type CONFIG. The following menu appears: RPC > CONFIG 1) . . . Change Password 2) . . . Change Outlet Name Enter Request: Select #2, “Change Outlet Name,” and press The RPC responds: 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . .
1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . Router 1 5) . . . OUTLET 5 6) . . . OUTLET 6 Enter Request: To return to the RPC > prompt, hit any key at the “Enter Request” prompt. 5.2.2 REMOTE ACCESS 5.2.2.1 MODEM CONNECTIONS RPC-2 MD01 (Internal Modem) Using the RJ04X007 (RJ-11) modular cable, connect either port labeled “LINE” on the back of the RPC unit to the telco wall jack. Proceed to “Accessing Main Menu via Modem.
IMPORTANT You must customize the external modem’s configuration to operate properly with the RPC-2 RDR. See Appendix C (MODEM COMMAND SUMMARY) for information on customizing external modem configurations. 5.2.2.2 REMOTE OPERATION The RPC’s main menu allows you to monitor and control the equipment attached to each of the RPC-2 RDR and RPC-2 MD01’s six receptacles. From this menu, the user can turn on, turn off, or reboot attached equipment, individually, or all equipment, simultaneously.
If prompted, enter password. The following main menu appears: RPC-2 Series (C) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . . OUTLET 6 : : : : : : Off Off Off Off Off Off VERY IMPORTANT WHEN OPERATING REMOTELY, DO NOT SEND THE COMMAND TO TURN “OFF” A RECEPTACLE THAT HAS A HOST TERMINAL OR MODEM ATTACHED. DOING SO WILL RESULT IN THE HOST TERMINAL OR MODEM BEING POWERED DOWN CREATING A “LOCKEDOUT” CONDITION.
Example: To turn “On” Outlet 3, type ON 3 from the RPC prompt (RPC >). The RPC responds: Turn On Outlet 3 (Y/N)? Responding “Y” for yes turns “On” Outlet 3. Observe the status of Outlet 3 has changed to On in the status menu: RPC-2 Series (c) 1997 by BayTech F2.07 Circuit Breaker : On 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . OUTLET 4 5) . . . OUTLET 5 6) . . .
5.3 RPC-3, RPC-3A and RPC-5 RPC-5 Note: The RPC-3 and RPC-5 are configured in a similar manner. This quick start will make reference the RPC-3 menus. The only programming differences for the RPC-5 pertain to the number of receptacles shown in the menus. Inlet #1 supplies power to the logic of the RPC-5, this inlet must have power for the unit to operate. The RPC-3 and RPC-3A are multi-user units, supporting one admin user and up to eight outlet users.
The RPC-3 and RPC-3A have an Ethernet port for connecting to a network. REMEMBER, in order for a network connection to be established, at a minimum, you must configure the IP address, subnet mask, and if applicable, gateway. Network configurations can be RPC 3 AND RPC 3A CONNECTION ____________________________________________________________ configured through the Ethernet port or locally through the serial port.
THAT HAS A HOST TERMINAL OR MODEM ATTACHED. DOING SO WILL RESULT IN THE HOST TERMINAL OR MODEM BEING POWERED DOWN CREATING A “LOCKEDOUT” CONDITION. YOU WILL NOT BE ABLE TO REESTABLISH A CONNECTION UNTIL THE RECEPTACLE HAS BEEN TURNED “ON” THROUGH THE SERIAL PORT.
Accessing Main Menu Power on the RPC unit. The following main menu appears: RPC-3 Telnet Host Revision F 3.03, (C) 1998 Bay Technical Associates Unit ID: RPC3 RPC-3 Menu: 1) . . . Outlet Control 2) . . . Manage Users 3) . . . Configuration 4) . . . Unit Status 5) . . . Reset Unit 6) . . . Logout Enter Selection: If the main menu fails to appear, ensure the correct cables and adapters are being used and they are properly connected. Also, verify the serial communication parameters are correctly configured.
NOTE The outlet user sees only those outlets as assigned to him by the admin user. From the RPC > prompt, enter one of the following commands: ON n, OFF n, REBOOT n, where “n” is the outlet number you wish to send the command. Entering an outlet number of “0” sends the command to all outlets. RPC OWNER’S MANUAL ____________________________________________________________ Example: To turn “On” Outlet 3, type ON 3 from the RPC prompt (RPC >).
command to REBOOT (n) is sent from the RPC > prompt, the RPC powers “Off” corresponding outlet(s) for approximately 10 seconds plus the programmed outlet delay time, then returns them to the state they were (“On” or “Off”) prior to receiving the reboot command. NOTE The reboot command will only reboot outlets that are turned ON; an outlet that is turned OFF cannot be rebooted. RPC-3 AND RPC-3A OPERATIONS ____________________________________________________________ 5.3.4.
2) 3) 4) 5) Add user . . . Delete user . . . admin . . . engineering . . . sales The “Add user” option is presented any time less than 8 optional users are defined. Select #1, “Add user,” from the User Management Menu. The RPC-3 or RPC-3A responds: Enter username (<= 8 characters) > Enter the name of the user to be added, followed by a carriage return . RPC OWNER’S MANUAL ____________________________________________________________ NOTE User name is case sensitive.
neither the username nor password is required, and every user will have access to all admin functions. From the User Management Menu, select the number of the user to modify, followed by a carriage return . The unit responds: RPC-3 AND RPC-3A OPERATIONS ____________________________________________________________ NOTE Password can be enabled or disabled for serial login and network login. Enter choice, CR to exit User name: engineering 1) 2) . . . Change Password . . .
RPC responds indefinitely with “Enter old password:” until the old password has been entered correctly. NOTE A carriage return will exit to user menu. If you enter the current password correctly, the RPC responds: Enter new password (<= 8 characters) > Enter a new password (maximum field length, 8 alphanumeric characters), followed by a carriage return.
return. The select #2, “Change Outlet List.” The RPC-3 or RPC-3A responds: To change outlet access, enter number(s) of outlets. If more than one entry, separate numbers with commas. CR to exit. User Name: engineering Outlet 1) . . . Outlet 1 2) . . . Outlet 2 3) . . . Outlet 3 4) . . . Outlet 4 5) . . . Outlet 5 6) . . . Outlet 6 7) . . . Outlet 7 8) . . .
5) . . . Access 6) . . . Outlets 7) . . . Exit IMPORTANT NETWORK PARAMETERS, SUCH AS IP ADDRESS, REQUIRE A UNIT RESET BEFORE ANY CHANGES WILL TAKE AFFECT. ALL OTHER CONFIGURATION CHANGES WILL BE IMMEDIATELY IMPLEMENTED UPON ACCEPTING CHANGES AT THE END OF THE CONFIGURATION PROCEDURE. EXIT ALL MENUS BY . IP Address The IP address consists of four bytes, each byte ranging from 0 to 255. This parameter must be programmed before the RPC can be accessed on the network.
Enter the Subnet Mask (Example: 255.255.255.0), followed by a carriage return. Upon entry of a carriage return, the RPC resumes the configuration menu. NOTE: The factory default Subnet Mask is 0.0.0.0. If you fail to enter the subnet mask in dotted decimal form, the RPC responds again: Enter Subnet Mask in dotted decimal form: The RPC responds indefinitely with the same request until the subnet mask is entered in the correct form.
Enter the RPC unit ID, followed by a carriage return. The RPC resumes the configuration menu. NOTE: The factory default Unit ID is RPC-3. Access IMPORTANT If username and password are disabled (factory default), outlet users will have access to all admin functions. Login Setup allows the user to enable or disable username and password login for both serial and network ports. If the features are enabled, the RPC requires username and password entry before allowing access to the unit.
NOTE A null password for any particular user disables the password login requirement for that user, even if prompt for password is enabled. Outlets From the configuration menu, select #6, “Outlets.” The following Outlet Operation Configuration Menu appears: Outlet Operation Configuration Menu Enter Request, CR to exit 1) . . . 2) . . . 3) . . . 4) . . . 5) . . .
If the enable/disable feature is disabled, the RPC will not ask to confirm the command. From the Outlet Operation Configuration Menu, select #2, “Command Confirmation.” Depending on whether confirmation is currently enabled or disabled, the RPC responds with the option to change the current status.
Enter the amount of time (seconds) to elapse before power is applied to the outlet. The RPC-3 or RPC-3A resumes the power-up delay status displaying the change. NOTE Maximum number of seconds is 599. Name Outlets “Name Outlets” allows the user to customize outlet name(s) to identify individual pieces of equipment attached to the RPC. The factory default outlet names are Outlet 1, Outlet 2, Outlet 3 . . . Outlet 8.
change the name of Receptacle 4 from Outlet 4 to Router 1, type Router 1 from the “Enter” prompt, followed by a carriage return. The RPC responds with the outlet name menu displaying the name change to Outlet 4: 1) . . . OUTLET 1 2) . . . OUTLET 2 3) . . . OUTLET 3 4) . . . Router 1 5) . . . OUTLET 5 6) . . . OUTLET 6 Enter Request: To return to the configuration menu, hit any key at the “Enter Request” prompt.
problems with the RPC unit or its network interface capabilities, “Unit Status” information can be used as a valuable troubleshooting aid. You may be asked to refer to the unit status when calling one of BayTech’s Application Engineers for support. From the main menu, select #4, “Unit Status.” The following Unit Status Menu appears: RPC Unit Status Menu 1) . . . 2) . . . 3) . . . 4) . . .
number of buffers left (30 or less) available to send data, and whether the receive queue status is available to receive data. From the Unit Status Menu, select #2, “Network Interface.” The following network information is provided: Network Status: Medium status: good Medium faults: 0 Xmit bufr errs: 0 Available send buffers: 29 Receive queue status: open Logged Users This option shows the number of active sessions.
Enter the number of the session to terminate. The RPC responds: Outlet Status The following table shows the status of all outlets: Outlet Status Selection Number 1 2 3 4 5 6 7 8 Outlet Name OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET Outlet Number 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Power Status Off Off Off Off Off Off Off Off RPC-3 AND RPC-3A RESET UNIT ____________________________________________________________ 5.3.
In the list below, “n” refers to selection number as displayed in Outlet Status. Any invalid input results in an input error message and returns the user to the command prompt. From the RPC3> prompt in Outlet Control, type HELP. The RPC responds with the following command summary information. RPC3 > “n” refers to selection number, as displayed in Outlet Status.
a. b. c. d. e. f. The RPC model type The unit’s serial number (located on the bottom of the unit). The devices that you have connected to the RPC unit. Provide a general description of the application you are using. What are you trying to accomplish? What cables and adapters are you using? What are the lengths of the cables? Who sold you the cables and adapters? The name of the emulation program you are using. Bay Technical Associates, Inc. 200 N. Second Street, P. O. Box 387 Bay St.
a. b. c. d. e. f. Call BayTech to get a Return Authorization Number. Without this number, BayTech will not accept warranty or no-charge returns. Choose a heavy cardboard box. Surround your unit with a minimum of two inches of insulation. Be sure to seal the box securely with strapping or packing tape. We do not recommend masking tape or cellophane tape. On the outside of the box, please write the Return Authorization Number. Ship the unit to the following address: Bay Technical Associates, Inc. 200 N.
RPC OWNER’S MANUAL ____________________________________________________________ APPENDIX A RPC TROUBLESHOOTING GUIDE PROBLEM SYMPTOM CAUSE SOLUTION No Menu Blank Screen Cables Adapters Parameters Ensure correct cables and adapters are being used and are connected properly.
(Specifications). Verify serial parameters are correctly configured. Password Doesn’t Work Returns to prompt Caps Lock Password feature is case sensitive. Type password exactly as it was originally entered. No menu when accessing thru external modem Blank Screen Modem settings disagree with RPC-2 RDR Cannot access RPC-3 through network port Blank Screen Various Enter AT modem commands to configure modem to operate with RPC. See Appendix D (Modem Command Summary). Note what the CX LED is doing.
Network session locks up No response from unit More than 4 sessions open Terminate 1 or more sessions. See logged Users, Page 56. Can’t get out of Outlet Control Returns to Outlet Control Menu Wrong command Type MENU Device not working No power, dead Call BayTech Applications Engineers. Need to download manual from web site www.baytechdcd.com Go to Product Manuals; scroll to “JUMP HERE FOR MANUALS.” Select desired manual.
network parameters parameters configure thru network port serial port RPC OWNER’S MANUAL ____________________________________________________________ APPENDIX B SPECIFICATIONS Power Receptacle Circuit Breaker EIA-232 70 RPC2 RPC2A RPC-2 RPC-2 RPC-3 MDO1 RDR Table 3.
Serial Port Network Interface Protocols Frame Types Modem Interface Modem Connectors Dimensions Weight modular connecto r (RJ-45) modular connector (RJ-45) modular connector (RJ-45) modular connector (RJ-45) modular connector (RJ-45) Ethernet, IEEE 802.3 compliance 10BASE-T (twisted pair RJ-45) TCP/IP & Telnet Ethernet II and SNAP modular connector (RJ-45) Ethernet, IEEE 802.3 compliance 10BASE-T (twisted pair RJ-45) TCP/IP & Telnet Ethernet II and SNAP modular connector (RJ-45) Ethernet, IEEE 802.
Mounting (Optional) Warranty 72 19” or 23” One year on parts and labor 19” or 23” One year on parts and labor DCD modem status DCD modem status RX & TX activity -Link RX & TX activity Link RX & TX activity Link 19” or 23” One year on parts and labor 19” or 23” One year on parts and labor 19” or 23” One year on parts and labor 19” or 23” One year on parts and labor 19” or 23” One year on parts and labor
RPC OWNER’S MANUAL ____________________________________________________________ APPENDIX C DIAGNOSTIC LED INDICATIONS To detect hardware, cabling, or configuration problems upon initialization of power, the RPC-3 and RPC-3A go through a diagnostic sequence. To help determine the cause of the problem, the RPC-3 and RPC-3A have a CX LED located on the front, right side of the unit. Upon initialization of power, refer to the table below for interpretation.
RPC OWNER’S MANUAL ____________________________________________________________ APPENDIX D 1.0 MODEM COMMAND SUMMARY 1.1 U.S. ROBOTIC MODEMS COMMAND INTERPRETATION AT&B1 Fixed Serial Port Rate AT&C1 Normal CD Operations (default) AT&D2 Normal DTR Operations (default) ATS0=1 Auto answer telephone line in 4 or fewer rings ATE0 Modem does not display keyboard commands.
RPC OWNER’S MANUAL ____________________________________________________________ APPENDIX D 1.0 MODEM COMMAND SUMMARY (Cont.) 1.2 ROCKWELL CHIP SET MODEMS COMMANDS INTERPRETATION ATS23=59 Fixed Serial Port Rate (default) AT&C1 Normal CD Operations (default) AT&D2 Normal DTR Operations (default) ATS0=1 Auto answer telephone line in 4 or fewer rings ATE0 Modem does not display keyboard commands.
—A— Adapter, 3, 6, 9, 11, 17, 22, 24, 25, 32, 38, 42 Application Engineers, 58 Asynchronous, 23 ATDT Commands, 9, 39 —C— Cable , 23 Cabling, 20 Circuit Breaker, 3, 6, 19, 26, 33, 66 Communications Software, 3, 6, 9, 11, 25, 32, 33, 39, 43 Computer Adapter, 22 Computer/Terminal Adapter, 21 Configuration, 4, 7, 13, 14, 16, 24, 25, 27, 34, 35, 37, 39, 62, 63 Current Password, 28, 36, 49 Installation, 17 Interface, 64 Internal Modem, 1, 38 Internal Relays, 18 IP Address, 13, 14, 42, 43, 51, 52, 70 —L— LED, 1
Serial Parameters, 3, 6, 25, 32, 43 Serial Port, 3, 6, 11, 13, 25, 32, 39, 42, 43, 67, 70 Status Menu, 3, 7, 19, 26, 28, 31, 33, 34, 35, 37, 41, 45, 46 —T— Telco Wall Jack, 9, 38 Telnet, 11, 43, 44, 60, 66, 68 —U— Unpacking, 17 77
BAYTECH REMOTE POWER CONTROL UNIT OWNER’S MANUAL Bay Technical Associates, Inc. Data Communications Products Division 200 N. Second Street, PO Box 387 Bay St. Louis, MS 39520 Made in USA Fax: 228-467-4551 Phone: 228-467-8231 Toll free: 800-523-2702 Web Site: www.baytechdcd.