Operating instructions

Tel: 01282 717171 Fax: 01282 717273 Web: www.protec.co.uk Email: sales@protec.co.uk
Technical Specification
6300 Control Panel Complies with EN 54-2 & 4
Models:- 6301 - Single Loop Panel
6302 - 2 Loop Panel
6304 - 4 Loop Panel
Specification:-
Power Supply Mains 230V ac nominal ± 10%.
Working Voltage 21.5 - 30V dc.
Temperature Range 0 - 40°C.
Maximum Humidity 85% Non-condensing.
Panel Model 6301 6302 6304
Standby Load (Mains Fail Condition) 90mA 115mA 170mA
Alarm Load (Mains Fail Condition) 210mA 260mA 345mA
Display Backlit liquid crystal display 2 lines of 40 characters.
Digital Addressable Loops 1,2 or 4 loops, each with 191 address capacity. Total panel capacity is restricted to 512 Input addresses
to comply with EN 54-2. Algo-Tec™ 6000 Protocol.
Total Loop Load 600mA per loop including all loop connected devices.
Zones 32 Zone LED’s plus twin red common fire indicators.
Integral Charger 3A dc Switch-mode.
Integral Battery 10Ah 24V sealed lead acid.
Remote Power Supply The Protec 9000/BC range of power supplies are compatible with the 6300 panels.
Dual path outputs and fault signalling, (4 wire plus 2 wire, 2 primary power, 2 signals, 2 secondary power).
Programmable Alarm Outputs 4 Monitored - Internal sounder circuits (1A rated @ 24V).
1 Set of non-monitored double-pole changeover contacts (1A rated @ 24V).
Up to 191 alarm outputs per loop with the use of additional loop O/P devices.
Alarm Load Maximum 3A with integral power supply unit.
Fault Monitoring Fully fault monitored to EN 54-2.
Fault Output Single pole changeover contacts (1A rated @ 24V).
Serial Communications Interface 4 wire (2 power, 2 data) for up to 4 repeat/mimic panels.
Secure Network To replace above serial interface when optional 6300 network card fitted to allow up to 32 panels /
repeaters to be securely networked (2 wire loop).
Auxiliary Output Supply 24V dc fused at 250mA.
Common Fire Output (fire station) 24V dc fully monitored output rated at 20mA. 1K EOL.
Common Fault Output (fire station) 24V dc fully monitored output rated at 20mA. 1K EOL.
RS232 Communications Interface 9 way ‘D’ type connector (Male). For program/text software upload/download.
Optional Integral Printer 40 character low noise thermal printer.
Dimensions (mm) 440(W) x 385(H) x 144(D).
Approvals (6301) LPCB Certificate No: 201ad/07, EC Certificate No: 0832-CPD-1474, Relevant Standard: EN 54-2 & 4.
(6302) LPCB Certificate No: 201ad/08, EC Certificate No: 0832-CPD-1475, Relevant Standard: EN 54-2 & 4.
(6304) LPCB Certificate No: 201ad/09, EC Certificate No: 0832-CPD-1476, Relevant Standard: EN 54-2 & 4.
Programmability
96 Input Groups System Wide First 32 have an independent programmable time-out delay.
96 Output Groups per Panel First 32 have an independent programmable delay for first 32 input groups.
Each is programmable as an alarm or control output.
32 Zonal Output Groups per Panel Each is activated by a separate zone input for zones 1 to 32.
Programmable master time-out.
Selectable coincidence detection.
24 programmable Non-latching addresses.
24 programmable Non-latching Fire addresses.
6300 Repeat Panel/
6300 Illuminated Zonal Mimic
Power Supply 24V dc from local power supply or internal charger and battery (230V ac required).
Standby Load 50mA.
Alarm Load 50mA.
Serial Communications Link 4 wire (2 power, 2 data) for up to 4 repeat/mimic panels.
Secure Network To replace above serial interface when optional 6300 network card fitted to allow up to
32 panels/repeats to be securely networked (2 wire loop).
Dimensions (mm) 440(W) x 385(H) x 144(W).
6300 Netcard Optional network card fitted to each control panel and repeat to be networked.
The network card replaces the serial communication link. Up to 32 panels/repeats can be securely
networked (2 wire loop).
Standby/Alarm Load 70mA per network card.
Company Policy is one of continuous improvement, we reserve the right to change specification without prior notice
Protec Fire Detection Plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT
Fire Detection - Addressable
MED1509 Issue 2 N 92-048-61C
Protec: South West
Tel: 0845 456 5392
Fax: 0845 456 5393
Protec: South East
Tel: 0845 456 5394
Fax: 0845 456 5395
Protec: Midlands
Tel: 0845 456 5398
Fax: 0845 456 5399
Protec: Yorkshire
Tel: 0845 456 5388
Fax: 0845 456 5389
Protec: North East
Tel: 0845 456 5396
Fax: 0845 456 5397
Protec: Scotland
Tel: 0845 456 5390
Fax: 0845 456 5391
Protec
Protec Fire Detection plc
LPCB ref. no. 201ad
MANAGEMENT
SYSTEMS