Operating instructions
ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE
Fire Detection - Addressable
Controls and Display 
All the functions of the Control Panel are accessed via 
a modern styled hinged lockable door, moulded from 
polycarbonate with a clear display viewing window.  
When opened the door reveals the panel controls and 
easy to follow operating instructions. These controls 
are SILENCE, SOUND ALARMS, RESET and ACCEPT 
plus a MENU push button to enable access to the 
user menu facilities. The control panel display consists 
of an 80 large character liquid crystal display, twin 
common fire LED indicators, 32 separate zonal fire LED’s, 
power on, pre-alarm, system fault, common fault, test 
and disablement LED’s. An optional integral low noise 
thermal printer is also available.
Liquid Crystal Display 
The 80, large character liquid crystal display will under 
normal quiescent conditions display the current date 
and time with the option to also display a 40-character 
user’s message such as site name. 
In an alarm or fault condition the LCD will display the 
device loop, address and zone number and up to 40 
characters of user definable location text, programmable 
on site using Protec 6300/WINTEXT windows based 
software.
Device Location Text
Windows based text software is supplied free of charge 
to our clients to enable you to enter the location text 
on to the disk supplied and hand to our commissioning 
engineer for loading into the panel during commissioning. 
This simple process allows you more flexibility enabling 
you to make any last minute changes & speed up the 
entire process.
Printer 
The integral printer is a 40-character low noise thermal 
printer. In operation the printer will provide on demand 
real time data of fire and fault conditions including time 
and date of events along with the device number and 
location text. By accessing the appropriate function 
from the user menu facility a variety of reports can 
be printed including the previous 100 incidents from 
the event log, the system devices configuration and 
programming matrix, devices which are becoming due 
for cleaning and the current status of all devices.
Power Supply
The 6301, 6302 and 6304 control panels can be supplied 
with an integral 3A dc switch mode charger and a 
24V 10Ah sealed lead acid battery. The system is also 
available, suitable for use with Protec 9000/BC range 
remote power supplies with an extensive range of 
battery and charger sizes.
On Site Programming 
The Protec Algo-Tec™ 6300 system is on site 
programmable. All of the commissioning configuration 
data can be entered and/or backed up using the 
Protec 6300/WINPROG windows based programming 
software via a PC. This feature enables the system 
to be re-configured and checked prior to attending 
site simplifying commissioning works on site, enabling 
text amendments to be carried out whilst on site and 
providing an invaluable remote backup should the need 
arise. The system configuration data can also be printed 
using the control panels optional in-built thermal printer.
6300 Repeat Panel
The Protec 6300 repeat panel can be connected to the 6300 control panel’s serial 
communications link connection, using a 4-core screened cable. 
If the 6300 secure network is utilised then the repeat panel should be connected to 
the secure network by adding the integral 6300 network card. The repeat panel has 
an identical display to the control panel including 80 character LCD and 32 zone fire 
LED’s. Full control of silence, accept, sound alarms and reset is included and can be 
disabled. The repeat panel is available as surface or recessed mounted with a moulded 
polycarbonate hinged door finished in storm grey, or optionally with polished solid brass 
or brushed stainless steel finish for recess mounting only.
6300 Hercules Colour Graphics System
The Protec Colour Graphics System is a Windows based PC package providing a 
graphical representation of large sites enabling the precise location of an incident to 
be readily identified enabling a prompt response. Using touch screen or mouse, the 
operator can track an incident and zoom from a site plan to intermediate plan listing 
floor levels, then zoom to a specific floor plan and if necessary then zoom to a specific 
detailed area within the floor plan showing the device in question. Colour prints of the 
maps can be printed automatically or on demand.
Repeat Panel
6300 Hercules Colour Graphics System