Operating instructions
ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE
Fire Detection - Addressable
Controls and Display
All the functions of the Control Panel are accessed via
a modern styled hinged lockable door, moulded from
polycarbonate with a clear display viewing window.
When opened the door reveals the panel controls and
easy to follow operating instructions. These controls
are SILENCE, SOUND ALARMS, RESET and ACCEPT
plus a MENU push button to enable access to the
user menu facilities. The control panel display consists
of an 80 large character liquid crystal display, twin
common fire LED indicators, 32 separate zonal fire LED’s,
power on, pre-alarm, system fault, common fault, test
and disablement LED’s. An optional integral low noise
thermal printer is also available.
Liquid Crystal Display
The 80, large character liquid crystal display will under
normal quiescent conditions display the current date
and time with the option to also display a 40-character
user’s message such as site name.
In an alarm or fault condition the LCD will display the
device loop, address and zone number and up to 40
characters of user definable location text, programmable
on site using Protec 6300/WINTEXT windows based
software.
Device Location Text
Windows based text software is supplied free of charge
to our clients to enable you to enter the location text
on to the disk supplied and hand to our commissioning
engineer for loading into the panel during commissioning.
This simple process allows you more flexibility enabling
you to make any last minute changes & speed up the
entire process.
Printer
The integral printer is a 40-character low noise thermal
printer. In operation the printer will provide on demand
real time data of fire and fault conditions including time
and date of events along with the device number and
location text. By accessing the appropriate function
from the user menu facility a variety of reports can
be printed including the previous 100 incidents from
the event log, the system devices configuration and
programming matrix, devices which are becoming due
for cleaning and the current status of all devices.
Power Supply
The 6301, 6302 and 6304 control panels can be supplied
with an integral 3A dc switch mode charger and a
24V 10Ah sealed lead acid battery. The system is also
available, suitable for use with Protec 9000/BC range
remote power supplies with an extensive range of
battery and charger sizes.
On Site Programming
The Protec Algo-Tec™ 6300 system is on site
programmable. All of the commissioning configuration
data can be entered and/or backed up using the
Protec 6300/WINPROG windows based programming
software via a PC. This feature enables the system
to be re-configured and checked prior to attending
site simplifying commissioning works on site, enabling
text amendments to be carried out whilst on site and
providing an invaluable remote backup should the need
arise. The system configuration data can also be printed
using the control panels optional in-built thermal printer.
6300 Repeat Panel
The Protec 6300 repeat panel can be connected to the 6300 control panel’s serial
communications link connection, using a 4-core screened cable.
If the 6300 secure network is utilised then the repeat panel should be connected to
the secure network by adding the integral 6300 network card. The repeat panel has
an identical display to the control panel including 80 character LCD and 32 zone fire
LED’s. Full control of silence, accept, sound alarms and reset is included and can be
disabled. The repeat panel is available as surface or recessed mounted with a moulded
polycarbonate hinged door finished in storm grey, or optionally with polished solid brass
or brushed stainless steel finish for recess mounting only.
6300 Hercules Colour Graphics System
The Protec Colour Graphics System is a Windows based PC package providing a
graphical representation of large sites enabling the precise location of an incident to
be readily identified enabling a prompt response. Using touch screen or mouse, the
operator can track an incident and zoom from a site plan to intermediate plan listing
floor levels, then zoom to a specific floor plan and if necessary then zoom to a specific
detailed area within the floor plan showing the device in question. Colour prints of the
maps can be printed automatically or on demand.
Repeat Panel
6300 Hercules Colour Graphics System