Technical data

35
13.0 Changing Components
© Baxi Heating UK Ltd 2012
Socket Headed
Screw
Pump Head
Pump Body
Automatic Air
Vent
Fig. 53
Fig. 54
Electrical Supply
Plug
Pump Flow
Pipe
13.10 Pump - Head Only (Fig. 53)
1. Disconnect the electrical supply plug from the pump.
2. Close the flow and return isolation taps and drain the
boiler primary circuit. Remove the socket head screws
securing the pump head to the body and draw the
head away.
3. Reassemble in reverse order.
13.11 Pump - Complete (Fig. 54)
1. Disconnect the electrical supply plug from the pump.
2. Close the flow and return isolation taps and drain the
boiler primary circuit. For ease of access remove the
heating pressure gauge (13.14).
3. Undo the three screws securing the body to the inlet
assembly and pump flow pipe. Draw the complete
pump forwards.
4. Pull off the securing clip and remove the automatic
air vent. Transfer them to the new pump body.
5. Examine the ‘O’ ring seals, replacing if necessary and
reassemble in reverse order.
13.12 Automatic Air Vent (Fig. 54)
1. For access on 12 - 28 models see Section 13.17 to
remove the expansion vessel. Close the flow and
return isolation taps and drain the primary circuit.
2. The automatic air vent is a bayonet fitting. Remove
by twisting anticlockwise.
3. Fit the new automatic air vent, ensuring the ‘O’ ring
is fitted and the cap is open . Reassemble in reverse
order.
Control Box removed
for clarity