SITE REQUIREMENTS – Page 15
Flue
An internal fitting kit is available for installations where the
flue terminal is inaccessible from the outside. -(Part No
236441). This is available from merchants or direct from Baxi
free of charge.
The following guidelines indicate the general requirements
for siting balanced flue terminals. Recommendations for
flues are given in BS 5440 Pt.1.
If the terminal is fitted within 1 metre (39 in) of a plastic
gutter, within 500mm (19 ½ in) of a painted eave or a
painted gutter, an aluminium shield of at least 1 metre (39 in)
long should be fitted to the underside of the gutter or painted
surface. An air space of 5mm (3/16 in) should be left
between shield and gutter.
If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance
and that the terminal will not obstruct the passageway.
Terminal Position with Minimum Distance (mm)
A Directly below an openable window or other
opening. e.g. an air brick. 300
B Below gutters. 25
C Below eaves, soil pipes or drain pipes. 75
D Below balconies or car port roof 200
E From vertical drain pipes and soil pipes. 75
F From internal or external corners. 25
G Above ground, roof or balcony level. 300
H From a surface facing a terminal. 600
I From a terminal facing a terminal. 1200
J Vertically from a terminal on the same wall. 1500
K Horizontally from a terminal on the same wall. 300
L For an opening in a car port (e.g. door, window)
into a dwelling. 1200