Technical data

© Baxi Heating UK Ltd 2010
23
Min. 11°C Max. 20°C
l/min
11.5
15.2
19.2
22.9
26.7
30.5
mbar
21.2
34.1
53.0
73.5
97.5
124.6
m
0.22
0.35
0.54
0.75
0.99
1.27
30 HE
40 HE
50 HE
60 HE
70 HE
80 HE
Water
level
22mm
Flow
Return
Top of
casing
Boiler
Max. 30.5m (100ft)
Min. 150mm (6")
Optional
2 port
valves
Indirect HE
Cylinder
Auto air vent
Alternative existing
by-pass arrangement
using the bathroom
radiator fitted with two
lockshield valves
Typical Fully Pumped System fitted with a Close Coupled Feed and Open Vent
** If plastic pipe is used for the central heating circuit there must be a run of at least
2 metres of uninsulated copper pipe from the boiler flow and return connections
including any branches.
2m **
Automatic
by-pass or
existing
by-pass
balancing
valve
Optional
3 port
valve
Auto air vent
150 mm
Max.
Boiler drain off
point inside casing
Pump with
isolating valves
Table 2
3.10.5 Boiler Protection
A frost thermostat is fitted within the boiler controls
which operates even if the temperature control knob
is at the ( ) position. The boiler will operate as
necessary to maintain the boiler temperature above
freezing.
The boiler is fitted with a timed pump overrun that will
operate for around 2 minutes after boiler shutdown.
The boiler control will operate the pump for around 2
minutes every 24 hours to maintain free running of
the pump.
3.10.6 Pump Requirements
Resistance through the heat exchanger is shown in
the graph and Table 2 opposite.
If other control valves are used in the system the
resistance through them, quoted in their
manufacturers literature must be taken into account.
3.10.7 Further Details
Further details on systems are shown in BS5449 and
BS6798
Fig. 30
l/min
6.3
8.4
10.6
12.6
14.7
16.8
mbar
6.3
10.8
16.9
23.7
31.9
41.2
m
0.06
0.11
0.17
0.24
0.32
0.42
Water Flow Rate (l/min) and Boiler Resistance (mbar/m)