User Manual

en_BA_U500_UR18_Gen2_IO-Link.docx 35/43 Baumer Electric AG
04.04.2019/ Frauenfeld, Switzerland
System Command (Teach
Apply)
wo
System Command (Teach
Cancel)
wo
5.2.1 Single Point / 1-Point Teach
If the selected SSC is configured as Single Point mode ( Changing the mode is explained in section 4.3.2.1),
following command sequence is required to teach-in SP1:
Command sequence:
- Place object at desired switching distance
- Execute Teach SP1 to teach-in the distance
- Execute Teach Apply to store the setpoint
By executing Teach Cancel the teach-in procedure can be canceled at any state, as long Teach Apply has
not been used before.
Figure 28 Single Point Teach, switching behavior
.P, .R, .D types
In this example, the hysteresis is configured to be
right aligned (See 4.3.2.4 for more details regarding
hysteresis alignment)
Figure 29 Single Point Teach, switching behavior
.R types
For more detailed information about the reflector
tolerance, see section 4.3.2.5.
5.2.2 Window Teach
If the selected SSC is configured to Window mode ( Changing the mode is explained in section 4.3.2.1),
following command sequence can be applied to teach-in SP1 and SP2
Command sequence:
- Place object at desired switching distance
- Execute Teach SP1 to teach-in the distance related to SP1
- Execute Teach SP2 to teach-in the distance related to SP2
- Execute Teach Apply to store the setpoint
By executing Teach Cancel the teach-in procedure can be canceled at any state as long Teach Apply has not
been used before.