User Manual
en_BA_U500_UR18_Gen2_IO-Link.docx  33/43  Baumer Electric AG 
04.04.2019/    Frauenfeld, Switzerland 
See Figure 27 for a graphical illustration of the teach-in procedure by using qTeach. 
Figure 27: Teach-In procedure Xpress by using qTeach 
4.8.3  qTeach Lock 
By default the qTeach is locked 5 min after power up to avoid any undesirable manipulation.  
This lock timeout can be deactivated completely or adjusted from 1 … 120 min. 
Only the qTeach is being affected. Teach-in by wire is always possible, it does not lock.. 
Parameter name 
Short Description 
Rights 
Unit / Allowed 
values 
Teach Lock Settings.qTeach Time 
Out 
Time until qteach is locked. 
If 0 qteach never locks. 
If 0xFF qteach always off 
rw 
0: Never locked 
1 …120:  locked 
after n minutes 
0xFF: Always 
locked 
Default: 5 min 
5  Teach Commands 
By using teach commands, the setpoints of the switching signal channels SSC1 and SSC2 or of the Analog 
output can be defined by teach-in the position of the object or reference. 
Next to teach-by-value which can be applied as described in section 4.3.1, using teach commands makes it 
easy to compensate individual variations such as mechanical and mounting tolerances. 
The teach-in procedures are described more detailed in section 5.2 (Static). 
The switching behavior of each switching signal channel depends on the configuration (Switching Mode, 
Channel Logic, …) described in section 4.3.2. 