User Manual
en_BA_U500_UR18_Gen2_IO-Link.docx  26/43  Baumer Electric AG 
04.04.2019/    Frauenfeld, Switzerland 
4.5  Quality Parameters 
This parameter indicates the signal strength from the received reflection relative to the set threshold. It is 
useful to be monitored by the PLC to detect weak signals which may be caused by misalginement or by dirt 
on the sensor surface. 
Parameter name 
Short Description 
Rights 
Unit / Allowed values 
Quality.Value 
Quality value indicates the quality of 
the reflected signal 
ro 
units dB 
Quality Bit.Threshold 
Selects the Quality Threshold, if the 
quality value is below the threshold 
the LEDs start to blink and the quality 
bit in the process data is set to 1 
rw 
Limits: 0 to 40 dB, units 
dB; Default 12 dB 
4.6  Temperature Settings 
The speed of sound depends strongly on the temperature. Therefore Baumer ultrasonic sensors are 
temperature corrected. When “internal temperature” is selected, the sensor will use temperature sensors 
located inside of the sensor to correct for variation in the speed of sound with respect to the ambient 
temperature. In order to improve the accuracy or to remove the warm up time, it is possible to use an 
external temperature sensor and set the temperature using the parameter “Temperature 
Settings.Environment Temperature”. When this is done the self heating of the sensor can be made 
irrelevant. The parameter “Temperature Settings.Enable Environment Temperature” has to be set to 
“External Temperature”.  
Parameter name 
Short Description 
Rights 
Unit / Allowed values 
Temperature 
Settings.Enable 
Environment Temperature 
Enable usage of external 
environment temperature.  
rw 
External Temperature / 
Internal Temperature 
Default: Internal 
Temperature 
Temperature Settings. 
Environment Temperature 
Sets the temperature that is used by 
sensor to calculate the distance. It is 
only used when the parameter 
"Temperature Settings.Enable 
External Environment temperature" is 
set to External Temperature. 
rw 
Limits : -40°C to 85°C 
Default: 20°C 
Unit Selection.Temperature 
Select temperature unit (rw 
parameter in menu Parameter/ 
Temperature Settings, ro in menu 
Diagnosis/ Device Temperature) 
rw 
Kelvin / Celsius / 
Fahrenheit 
Default: Celsius 
Unit Selection.Time 
Select time unit (rw parameter in 
menu Parameter/ Temperature 
Settings, ro in menu Diagnosis/ 
Operating Time) 
rw 
Second / Minute / Hour 
Default: Second 