User Manual

en_BA_U500_UR18_Gen2_IO-Link.docx 21/43 Baumer Electric AG
04.04.2019/ Frauenfeld, Switzerland
4.3.3.3 Minimal Pulse Duration
The minimal pulse duration defines the minimum time, the switching signal of the related SSC stays active or
inactive after the change of its status.
This parameter can be applied on
- both slopes / active and inactive
- positive slope / active (or inactive, if the logic is inverted as described in section 4.3.2.1)
- negative slope / inactive (or active, if the logic is inverted as described in section 4.3.2.1)
When to apply?
- To align the timing of the sensor to a slower PLC.
- To avoid bouncing.
- To avoid false pulses due to short losses of a proper signal.
- To straighten the clock / pace
Figure 21 Minimum Pulse Duration
Parameter name
Short Description
Rights
Unit /
Allowed
values
Minimal Pulse Duration.SSC1 Time
Sets / indicates the minimal pulse
length in milliseconds for the
respective switching signal channel
(SSC).
rw
0 to 60.000 ms
Default: 0 ms
Minimal Pulse Duration.SSC1 Mode
0: Both Pulses: positive and
negative pulses are prolonged; 1:
Positive Pulse: only positive pulses
are prolonged; 2: Negative Pulse:
only negative pulses are prolonged
rw
-Both Slopes
(Default)
-Positive Slope
-Negative Slope