4.3.3.3  Minimal Pulse Duration 
The minimal pulse duration defines the minimum time, the switching signal of the related SSC stays active or 
inactive after the change of its status. 
This parameter can be applied on  
-  both slopes / active and inactive 
-  positive slope / active (or inactive, if the logic is inverted as described in section 4.3.2.1) 
-  negative slope / inactive (or active, if the logic is inverted as described in section 4.3.2.1) 
When to apply? 
-  To align the timing of the sensor to a slower PLC. 
-  To avoid bouncing. 
-  To avoid false pulses due to short losses of a proper signal. 
-  To straighten the clock / pace 
Figure 21 Minimum Pulse Duration 
Parameter name 
Short Description 
Rights 
Unit / 
Allowed 
values 
Minimal Pulse Duration.SSC1 Time 
Sets / indicates the minimal pulse 
length in milliseconds for the 
respective switching signal channel 
(SSC). 
rw 
0 to 60.000 ms 
Default: 0 ms 
Minimal Pulse Duration.SSC1 Mode 
0: Both Pulses: positive and 
negative pulses are prolonged; 1: 
Positive Pulse: only positive pulses 
are prolonged; 2: Negative Pulse: 
only negative pulses are prolonged 
rw 
-Both Slopes 
(Default) 
-Positive Slope 
-Negative Slope 